Number Description
Warning
Alarm/
Trip
Alarm/
Trip Lock
Parameter
Reference
91
Analog input 54 wrong settings
–
–
X
S202
99
Locked rotor
–
X
X
–
101
Speed monitor
X
X
–
104
Mixing fans
X
X
–
–
122
Mot. rotat. unexp.
–
X
–
–
123
Motor mod. changed
–
X
–
–
163
ATEX ETR cur.lim.warning
X
–
–
164
ATEX ETR cur.lim.alarm
–
X
–
–
165
ATEX ETR freq.lim.warning
X
–
–
166
ATEX ETR freq.lim.alarm
–
X
–
–
210
Position tracking
X
X
–
Parameter 4-70 Position Error Function
,
parameter 4-71 Maximum Position Error
,
parameter 4-72 Position Error Timeout
211
Position limit
X
X
–
Parameter 3-06 Minimum Position
,
parameter 3-07 Maximum Position
,
parameter 4-73 Position Limit Function
212
Homing not done
–
X
–
Parameter 17-80 Homing Function
213
Homing timeout
–
X
–
Parameter 17-85 Homing Timout
214
No sensor input
–
X
–
–
220
Configuration File Version not supported
X
–
–
–
246
Pwr.card supply
–
–
X
–
250
New spare part
–
–
X
–
251
New type code
–
X
X
–
430
PWM Disabled
–
X
–
–
Table 6.4 Alarm/Warning Code List
(X) Dependent on parameter.
1) Cannot be auto reset via parameter 14-20 Reset Mode.
A trip is the action following an alarm. The trip coasts the motor and is reset by pressing [Reset] or by a digital input
(
parameter group 5-1* Digital Inputs
). The original event that caused an alarm cannot damage the frequency converter or
cause dangerous conditions. A trip lock is an action when an alarm occurs, which could damage the frequency converter or
connected parts. A trip lock situation can only be reset by a power cycling.
Warning
Yellow
Alarm
Flashing red
Trip locked
Yellow and red
Table 6.5 Indicator Light