Parameter
Default setting
Parameter 0-01 Language
English
Parameter 0-20 Display Line 1.1 Small
Speed [RPM]
Parameter 0-21 Display Line 1.2 Small
Motor Current
Parameter 0-22 Display Line 1.3 Small
Power [kW]
Parameter 0-23 Display Line 2 Large
Frequency
Parameter 0-24 Display Line 3 Large
Reference %
Parameter 15-51 Frequency Converter Serial
Number
–
Table 4.8 Q1 My Personal Menu Settings, FC 302
4.3.3.3 Q2 Quick Setup
The parameters in
Q2 Quick Setup
are the basic parameters
that are always necessary for set-up. This menu provides
the most efficient set-up for most applications. Perform the
unit set-up in the order listed. See
for the set-up steps.
4.3.3.4 Q5 Changes Made
Select
Q5 Changes Made
to get information about:
•
The 10 most recent changes.
•
Changes made from default setting.
4.3.3.5 Q6 Loggings
Use
Q6 Loggings
for fault finding.
To get information about the display line readout, select
Loggings
. The information is shown as graphs. Only display
parameters selected in
parameter 0-20 Display Line 1.1
Small
and
parameter 0-24 Display Line 3 Large
can be
viewed. It is possible to store up to 120 samples in the
memory for later reference.
Q6 Loggings
Parameter 0-20 Display Line 1.1 Small
Speed [RPM]
Parameter 0-21 Display Line 1.2 Small
Motor current
Parameter 0-22 Display Line 1.3 Small
Power [kW]
Parameter 0-23 Display Line 2 Large
Frequency
Parameter 0-24 Display Line 3 Large
Reference %
Table 4.9 Loggings Parameter Examples
4.3.3.6 Main Menu Mode
The LCP provides access to the
Main Menu
mode. Select
the
Main Menu
mode by pressing the [Main Menu] key.
The resulting readout appears on the LCP display.
130BP066.12
Keypad Set-Up
Parameter Data Set
Parameter Data Check
Drive Information
18.4% 5.22A
Main Menu
1(1)
07 Motor Setup
Illustration 4.3 Main Menu View
Lines 2 through 5 on the display show a list of parameter
groups that can be selected via the
▲
and
▼
keys.
All parameters can be changed in the Main Menu. Option
cards added to the unit enable extra parameters associated
with the option device.
4.4 Programming the Drive System
For detailed information on the key functions on the local
control panel (LCP), see
chapter 4.3 Local Control Panel
. For information on parameter settings, see
chapter 4.7 Parameter Settings
Parameter overview
Parameter settings control the operation of the drive
system, and are accessed via the LCP. These settings are
assigned a default value at the factory, but customers can
configure them for their unique application. Each
parameter has a name and number that remain the same
regardless of the programming mode.
In the Main Menu mode, the parameters are divided into
groups. The first digit of the parameter number (from the
left) indicates the parameter group number. The parameter
group is then broken down into sub-groups, if necessary.
For example:
0-** Operation/Display
Parameter group
0-0* Basic Settings
Parameter sub-group
Parameter 0-01 Language
Parameter
Parameter 0-02 Motor Speed Unit
Parameter
Parameter 0-03 Regional Settings
Parameter
Table 4.10 Example of Parameter Group Hierarchy
Commissioning
User Guide
MG37L202
Danfoss A/S © 08/2017 All rights reserved.
17