Moving around the parameters
Navigate through the parameters using the following LCP
keys:
•
Press [
▲
] [
▼
] to scroll up or down.
•
Press [
◄
] [
►
] to shift a space to the left or right of
a decimal point while editing a decimal
parameter value.
•
Press [OK] to accept the change or [Cancel] to
disregard the change and exit edit mode.
•
Press [Back] twice to show the status screen, or
press [Main Menu] once to go back to the main
menu.
Danfoss has a software program available for developing,
storing, and transferring drive system programming. The
MCT 10 Set-up Software allows the installer or operator to
connect a PC to the drive system and perform live
programming, rather than using the LCP. Also, this software
can be used to do all the programming offline and then
simply download it to the drive system. As a further
option, the entire drive system profile can be loaded onto
the PC for back-up storage or analysis.
The USB connector or RS485 terminal of the drive system
can be used to connect the PC for programming and
downloads.
For information, and to download the basic version of MCT
10 Set-up Software, see
www.danfoss.com/BusinessAreas/
DrivesSolutions/SMCT10/MCT10+Downloads.htm
.
The advanced version can be obtained on a CD by
requesting part number 130B1000. For detailed
information on how to program using the MCT 10 Set-up
Software, refer to the
VLT
®
Motion Control Tools MCT 10 Set-
up Software Operating Instructions
.
4.4.1 Entering System Information
NOTICE
SOFTWARE DOWNLOAD
For commissioning using a PC, install MCT 10 Set-up
Software. The software is available for download (basic
version) or for ordering (advanced version, code number
130B1000). For more information and downloads, see
www.danfoss.com/BusinessAreas/DrivesSolutions/Software
+MCT10/MCT10+Downloads.htm
.
To enter basic system information into the drive system,
use the following steps. Recommended parameter settings
are intended for startup and check-out purposes.
Application settings vary.
1.
Press [Main Menu] on the LCP.
2.
Select
0-** Operation/Display
and press [OK].
3.
Select
0-0* Basic Settings
and press [OK].
4.
Select
parameter 0-03 Regional Settings
and press
[OK].
5.
Select
[0] International
or
[1] North America
as
appropriate and press [OK]. (This action changes
the default settings for several basic parameters).
6.
Press [Quick Menu] on the LCP.
7.
Change the following parameter settings if
necessary. The motor data is found on the motor
nameplate.
NOTICE
These steps assume that an asynchronous motor is used,
but the VLT
®
Parallel Drive Modules drive system does
support permanent magnet motors. For more
information on permanent magnet motors, see the
VLT
®
AutomationDrive FC 301/FC 302 Programming Guide
.
Parameter
Default setting
Parameter 0-01 Language
English
Parameter 0-20 Display Line 1.1 Small
Power size dependent
Parameter 0-22 Display Line 1.3 Small
Power size dependent
Parameter 0-23 Display Line 2 Large
Power size dependent
Parameter 0-24 Display Line 3 Large
Power size dependent
Parameter 1-25 Motor Nominal Speed
Power size dependent
Parameter 5-12 Terminal 27 Digital
Input
Coast inverse
Parameter 3-02 Minimum Reference
0.000 RPM
Parameter 3-03 Maximum Reference
1500.000 RPM
Parameter 3-41 Ramp 1 Ramp Up Time
Power size dependent
Parameter 3-42 Ramp 1 Ramp Down
Time
Power size dependent
Parameter 3-13 Reference Site
Linked to Hand On/Auto
On
Parameter 1-29 Automatic Motor
Adaptation (AMA)
Off
Table 4.11 Quick Setup Settings
NOTICE
MISSING INPUT SIGNAL
When the LCP shows AUTO REMOTE COASTING or
alarm
60, External Interlock
, the unit is ready to operate but is
missing an input signal. See
for details.
Commissioning