2.6.3 Immunity Requirements
The immunity requirements for frequency converters
depend on the environment in which they are installed.
The requirements for the industrial environment are higher
than the requirements for the home and office
environment. All Danfoss frequency converters comply
with the requirements for the industrial environment.
Therefore, the frequency converters also comply with the
lower requirements for home and office environment with
a large safety margin.
To document immunity against burst transient from
electrical phenomena, the following immunity tests have
been carried in accordance with the following basic
standards:
•
EN 61000-4-2 (IEC 61000-4-2): Electrostatic
discharges (ESD): Simulation of electrostatic
discharges from human beings.
•
EN 61000-4-3 (IEC 61000-4-3): Incoming electro-
magnetic field radiation, amplitude modulated
simulation of the effects of radar and radio
communication equipment, as well as mobile
communications equipment.
•
EN 61000-4-4 (IEC 61000-4-4): Burst transients:
Simulation of interference brought about by
switching a contactor, relay, or similar devices.
•
EN 61000-4-5 (IEC 61000-4-5): Surge transients:
Simulation of transients brought about for
example by lightning that strikes near instal-
lations.
•
EN 61000-4-6 (IEC 61000-4-6): RF common mode:
Simulation of the effect from radio-transmission
equipment joined by connection cables.
Basic standard
Burst IEC 61000-4-4
Surge IEC 61000-4-5 ESD IEC 61000-4-2
Radiated electro-
magnetic field
IEC 61000-4-3
RF common mode
voltage
IEC 61000-4-6
Acceptance criterion
B
B
B
A
A
Line (no screen)
4 kV
2 kV/2 Ω DM
4 kV/12
Ω
CM
–
–
10 V
rms
LCP cable
2 kV
2 kV/2 Ω
1)
–
–
10 V
rms
Control wires
2 kV
2 kV/2 Ω
1)
–
–
10 V
rms
External 24 V DC
2 kV
2 kV/2
Ω
1)
–
–
10 V
rms
Relay wires
2 kV
42 kV/42
Ω
–
–
10 V
rms
Enclosure
–
–
8 kV AD
6 kV CD
10 V/m
–
Table 2.4 Immunity Requirements
1) Injection on cable screen.
Abbreviations:
AD - air discharge.
CD - contact discharge.
CM - common mode.
DM - difference mode.
Product Overview
Design Guide
MG03M202
Danfoss A/S © 06/2016 All rights reserved.
25