Key
Dual-speed
operation
Dual-mode
operation
Dual-direction
operation
Key +/-
Set reference
Key I
Run with reference Run with set-up 1 Run forward
Key II
Run with Jog
Run with set-up 2 Run reverse
Key O
Stop + Reset
Table 3.12 Function
Terminal Dual-speed
operation
Dual-mode
operation
Dual-direction
operation
18
Purple
Gray
19
–
27
Brown
29
Green
12
Red
50
Yellow
55
Blue
Table 3.13 Electrical Connections
Parameter
Dual-speed
operation
Dual-mode
operation
Dual-direction
operation
Parameter 5-10
Terminal 18
Digital Input
Terminal 18
Start*
Parameter 5-12
Terminal 27
Digital Input
Terminal 27
Reset
Parameter 5-13
Terminal 29
Digital Input
Terminal 29
Jog*
Select set-up
Start reversing
More
parameters
Parameter 3-
11 Jog Speed
[Hz]
Parameter 0-10
Active Set-up
=
[9] Multi set-
up
Parameter 4-10 M
otor Speed
Direction
=
[2]
Both directions
Table 3.14 Parameter Settings
* Indicates factory setting.
Alarms are reset at every start. To avoid this reset, either:
•
Leave the brown wire unconnected, or
•
Set
parameter 5-12 Terminal 27 Digital Input
to
[0]
No operation
.
At power-up, the unit is always in stop mode. The set
reference is stored during power-down.
To set permanent start mode, disable the stop function on
the LOP as follows:
•
Connect terminal 12 to terminal 18.
•
Do not connect purple/grey wire to terminal 18.
3.5 Special Conditions
3.5.1 Purpose of Derating
Consider derating when using the frequency converter:
•
At low air pressure (high altitudes).
•
At low speeds.
•
With long motor cables.
•
Cables with a large cross-section.
•
At high ambient temperature.
This section describes the actions required.
3.5.2 Derating for Ambient Temperature
and Switching Frequency
Refer to
chapter 6.10 Derating According to Ambient
Temperature and Switching Frequency
in this manual.
3.5.3 Automatic Adaptations to Ensure
Performance
The frequency converter constantly checks for critical levels
of:
•
Internal temperature.
•
Load current.
•
High voltage on the DC link.
•
Low motor speeds.
As a response to a critical level, the frequency converter
can adjust the switching frequency and/or change the
switching pattern to ensure the performance of the
frequency converter. The capability for automatic output
current reduction extends the acceptable operating
conditions even further.
3.5.4 Derating for Low Air Pressure
The cooling capability of air is decreased at lower air
pressure.
•
Below 1000 m altitude no derating is necessary.
•
Above 1000 m altitude, reduce the ambient
temperature or the maximum output current.
-
Reduce the output by 1% per 100 m
altitude above 1000 m, or
-
Reduce the maximum ambient
temperature by 1
°
C per 200 m altitude.
•
Above 2000 m altitude, contact Danfoss regarding
PELV.
System Integration
VLT
®
DriveMotor FCP 106/FCM 106
40
Danfoss A/S © 06/2016 All rights reserved.
MG03M202
3