6.2 Electrical Data
6.2.1 Mains Supply 3x380–480 V AC Normal and High Overload
Enclosure
MH1
MH2
MH3
PK55
PK75
P1K1
P1K5
P2K2
P3K0
P4K0
P5K5
Overload
1)
NO
HO
NO
HO
NO
HO
NO
HO
NO
HO
NO
HO
NO
HO
Typical shaft
output [kW]
0.55
0.75
1.1
1.5
2.2
3.0
4.0
Typical shaft
output [hp]
0.75
1.0
1.5
2.0
3.0
4.0
5.0
Maximum cable
cross-section in
terminals
2)
(mains, motor)
[mm
2
/AWG]
4/12
4/12
4/12
4/12
4/12
4/12
4/12
Output current
40
°
C ambient temperature
Continuous
(3x380–440 V) [A]
1.7
2.2
3.0
3.7
5.3
7.2
9.0
Intermittent
(3x380–440 V) [A]
1.9
2.7
2.4
3.5
3.3
4.8
4.1
5.9
5.8
8.5
7.9
11.5
9.9
14.4
Continuous
(3x440–480 V) [A]
1.6
2.1
2.8
3.4
4.8
6.3
8.2
Intermittent
(3x440–480 V) [A]
1.8
2.6
2.3
3.4
3.1
4.5
3.7
5.4
5.3
7.7
6.9
10.1
9.0
13.2
Maximum input current
Continuous
(3x380–440 V) [A]
1.3
2.1
2.4
3.5
4.7
6.3
8.3
Intermittent
(3x380–440 V) [A]
1.4
2.0
2.3
2.6
2.6
3.7
3.9
4.6
5.2
7.0
6.9
9.6
9.1
12.0
Continuous
(3x440–480 V) [A]
1.2
1.8
2.2
2.9
3.9
5.3
6.8
Intermittent
(3x440–480 V) [A]
1.3
1.9
2.0
2.5
2.4
3.5
3.2
4.2
4.3
6.3
5.8
8.4
7.5
11.0
Maximum mains
fuses
See
chapter 6.9 Fuse and Circuit Breaker Specifications
Estimated power
loss [W], best
case/typical
3)
38
44
57
73
91
129
143
Efficiency [%], best
case/typical
4)5)
0.96
0.97
0.97
0.97
0.97
0.97
0.97
Table 6.11 Mains Supply 3x380–480 V AC Normal and High Overload: MH1, MH2, and MH3 Enclosure
1) NO: Normal overload, 110% for 1 minute. HO: High overload, 160% for 1 minute.
A frequency converter intended for HO requires a corresponding motor rating. For example, Table 6.11 shows that a 1.5 kW motor for HO requires
a P2K2 frequency converter.
2) Maximum cable cross-section is the largest cable cross-section that can be attached to the terminals. Always observe national and local
regulations.
3) Applies to dimensioning of frequency converter cooling. If the switching frequency is higher than the default setting, the power losses may
increase. LCP and typical control card power consumptions are included. For power loss data according to EN 50-598-2, refer to
www.danfoss.com/vltenergyefficiency.
4) Efficiency measured at nominal current. For energy efficiency class, see chapter 6.5 Ambient Conditions. For part load losses, see
www.danfoss.com/vltenergyefficiency.
5) Measured using 4 m screened motor cables at rated load and rated frequency.
Specifications
Design Guide
MG03M202
Danfoss A/S © 06/2016 All rights reserved.
65
6