2.2.1 Configuring with the VLT
®
Memory
Module MCM 101
When replacing or adding a frequency converter to a
system, it is easy to transfer existing data to the new
frequency converter. However, the frequency converters
must be of the same power size and with compatible
hardware.
WARNING
DISCONNECT POWER BEFORE SERVICING!
Before performing repair work, disconnect the frequency
converter from AC mains. After mains has been discon-
nected, wait 4 minutes for the capacitors to discharge.
Failure to follow these steps can result in death or
serious injury.
1.
Remove the lid from a frequency converter
containing a memory module.
2.
Unplug the memory module.
3.
Place and tighten the lid.
4.
Remove the lid from the new frequency
converter.
5.
Insert the memory module in the new/other
frequency converter and leave it in.
6.
Place and tighten the lid on the new frequency
converter.
7.
Power up the frequency converter.
NOTICE
The first power-up takes approximately 3 minutes.
During this time, all data is transferred to the new
frequency converter.
2.2.2 Copying Data via PC and Memory
Module Programmer (MMP)
By using a PC and the MMP, it is possible to create several
memory modules with the same data. These memory
modules can then be inserted in a number of VLT
®
DriveMotor FCP 106 or VLT
®
DriveMotor FCM 106.
Examples of data that can be copied are:
•
Firmware.
•
Parameter set-up.
•
Pump curves.
While running, the download status is visible on the
screen.
1.
Connect an FCP 106 or FCM 106 to a PC.
2.
Transfer the configuration data from the PC to
the frequency converter. This data is NOT
encoded.
Parameter list
Firmware
Motor database
..
.
Not encoded data
195NA502.10
Illustration 2.9 Data Transfer from PC to Frequency Converter
3.
The data is automatically transferred from the
frequency converter to the memory module as
encoded data.
Encoded data
MCM
195NA503.10
Illustration 2.10 Data Transfer from Frequency Converter to
Memory Module
Product Overview
Design Guide
MG03M202
Danfoss A/S © 06/2016 All rights reserved.
15
2
2