Figure 9.6 Rotation Direction
9.4 Resolver Option MCB 103
MCB 103 Resolver option is used for interfacing resolver
motor feedback to VLT
®
AutomationDrive. Resolvers are
used as motor feedback devices for permanent magnet
brushless synchronous motors.
When the resolver option is ordered separately, the kit
includes:
•
Resolver option MCB 103
•
Enlarged LCP fixture and enlarged terminal cover
Selection of parameters:
17-5* Resolver Interface
.
MCB 103 Resolver Option supports a various number of
rotor resolver types.
Resolver Poles
17-50 Poles
: 2 *2
Resolver Input
Voltage
17-51 Input Voltage
: 2.0–8.0 Vrms *7.0 Vrms
Resolver Input
Frequency
17-52 Input Frequency
: 2–15 kHz
*10.0 kHz
Transformation ratio
17-53 Transformation Ratio
: 0.1–1.1 *0.5
Secondary input
voltage
Max 4 Vrms
Secondary load
App. 10 k
Ω
Table 9.3 Resolver Specifications
Resolver Input
SW. ver. X.XX
MCB 103
Code No.
Option B
Rotor
Resolver
stator
Motor
LED 1 REF OK
LED 2 COS OK
LED 3 SIN OK
LED NA
130BA247.11
REF+
REF-
COS-
COS+
SIN+
SIN-
S4
S2
S3
S1
R2
R1
COS
-
COS+
REF+ REF-
SIN+ SIN- A+ A
-
B+ B- Z+ Z-
X32/
3
1 2
4 5
11
6
8
7
10
9
12
1
2
3
4
S1
S3
S4
S2
R1
R2
θ
Figure 9.7 Resolver Option MCB 103 used with a Permanent
Magnet Motor
NOTICE!
The Resolver Option MCB 103 can be used with only
rotor-supplied resolver types. Stator-supplied resolvers
cannot be used.
LED Indicators
The LEDs are active when
17-61 Feedback Signal Monitoring
is set to
Warning
or
Trip
.
LED 1 is on when the reference signal is OK to resolver
LED 2 is on when cosine signal is OK from resolver
LED 3 is on when sinus signal is OK from resolver
Options and Accessories
Design Guide
254
Danfoss A/S © Rev. 2014-02-10 All rights reserved.
MG34S222
9
9