525 V, 50 Hz
575 V, 60 Hz
690 V, 50 Hz
Frame size
Filter ordering number
[kW]
[A]
[HP]
[A]
[kW]
[A]
IP00
IP23
45
76
60
73
55
73
D1h/D3h/D5h/D6h
130B4116
130B4117
55
90
75
86
75
86
D1h/D3h/D5h/D6h
130B4118
130B4119
75
113
100
108
90
108
D1h/D3h/D5h/D6h
130B4118
130B4119
90
137
125
131
110
131
D1h/D3h/D5h/D6h
130B4121
130B4124
110
162
150
155
132
155
D1h/D3h/D5h/D6h
132
201
200
192
160
192
D2h/D4h, D7h/D8h
130B4125
130B4126
160
253
250
242
200
242
D2h/D4h, D7h/D8h
200
303
300
290
250
290
D2h/D4h, D7h/D8h
130B4129
130B4151
250
360
350
344
315
344
D2h/D4h, D7h/D8h, F8/F9
350
344
355
380
F8/F9
130B4152
130B4153
315
429
400
400
400
410
F8/F9
400
410
E1/E2, F8/F9
130B4154
130B4155
355
470
450
450
450
450
E1/E2, F8/F9
400
523
500
500
500
500
E1/E2, F8/F9
450
596
600
570
560
570
E1/E2, F8/F9
130B4156
130B4157
500
630
650
630
630
630
E1/E2, F8/F9
500
659
630
630
F1/F3, F10/F11
2X130B4129
2X130B4151
650
630
F1/F3, F10/F11
2X130B4152
2X130B4153
560
763
750
730
710
730
F1/F3, F10/F11
670
889
950
850
800
850
F1/F3, F10/F11
2X130B4154
2X130B4155
750
988
1050
945
900
945
F1/F3, F10/F11
750
988
1050
945
900
945
F2/F4, F12/F13
3X130B4152
3X130B4153
850
1108
1150
1060
1000
1060
F2/F4, F12/F13
1000
1317
1350
1260
1200
1260
F2/F4, F12/F13
3X130B4154
3X130B4155
Table 5.22 Sine-Wave Filter Modules 525–690 V
NOTICE!
When using sine-wave filters, ensure that the switching frequency complies with filter specifications in
14-01 Switching
Frequency
.
See also
Advanced Harmonic Filters Design Guide
.
How to Order
Design Guide
106
Danfoss A/S © Rev. 2014-02-10 All rights reserved.
MG34S222
5
5
Содержание VLT AutomationDrive FC 300