Figure 7.34 Different Parallel Connections of Motors
A
Installations with cables connected in a common joint as shown in A and B are only recommended for short cable lengths.
B
Be aware of the maximum motor cable length specified in
chapter 4.3 General Specifications
.
C
The total motor cable length specified in
chapter 4.3 General Specifications
is valid as long as the parallel cables are kept short less
than 10 m each. (Example 1).
D
Consider voltage drop across the motor cables. (Example 1).
E
Consider voltage drop across the motor cables. (Example 2).
F
The total motor cable length specified in
chapter 4.3 General Specifications
is valid as long as the parallel cables are kept less than
10 m each. (Example 2).
Table 7.65 Legend to
Electrical Installation
Design Guide
MG34S222
Danfoss A/S © Rev. 2014-02-10 All rights reserved.
221
7
7