4.3 General Specifications
Line Power Supply
Supply terminals (6-Pulse)
L1, L2, L3
Supply terminals (12-Pulse)
L1-1, L2-1, L3-1, L1-2, L2-2, L3-2
Supply voltage
380–500 V
±
10%
Supply voltage
FC 302: 525–690 V
±
10%
AC line voltage low/line drop-out:
During low AC line voltage or a line drop-out, the adjustable frequency drive continues until the intermediate circuit voltage
drops below the minimum stop level, which corresponds typically to 15% below the adjustable frequency drive's lowest rated
supply voltage. Power-up and full torque cannot be expected at AC line voltage lower than 10% below the adjustable frequency
drive's lowest rated supply voltage.
Supply frequency
50/60 Hz
±
5%
Max. temporary imbalance between line phases
3.0% of rated supply voltage
True power factor (
λ
)
≥
0.9 nominal at rated load
Displacement Power Factor (cos
ϕ
)
near unity (
>
0.98)
Switching on input supply L1, L2, L3 (power-ups)
≥
90 kW
Maximum 1 time/2 min.
Environment according to EN60664-1
Overvoltage category III/pollution degree 2
The unit is suitable for use on a circuit capable of delivering not more than 100,000 RMS symmetrical Amperes, 240/500/600/690
V maximum.
Motor Output (U, V, W)
Output voltage
0–100% of supply voltage
Output frequency (125–1350 hp [90–1000 kW])
0–590
1)
Hz
Output frequency in flux mode (FC 302 only)
0–300 Hz
Switching on output
Unlimited
Ramp times
0.01–3600 s
1)
Voltage and power dependent.
Torque Characteristics
Starting torque (Constant torque)
maximum 160% for 60 s
1)
Starting torque
maximum 180% up to 0.5 s
1)
Overload torque (Constant torque)
maximum 160% for 60 s
1)
Starting torque (Variable torque)
maximum 110% for 60 s
1)
Torque rise time in VVC
plus
(independent of fsw)
10 ms
Torque rise time in FLUX (for 5 kHz fsw)
1 ms
1) Percentage relates to the nominal torque.
2) The torque response time depends on application and load but as a general rule, the torque step from 0 to reference is 4–5 x
torque rise time.
Cable Lengths and Cross-sections for Control Cables
1)
Max. motor cable length, shielded
500 ft [150 m]
Max. motor cable length, non-shielded
1,000 ft [300 m]
Maximum cross-section to control terminals, flexible/rigid wire without cable end sleeves
1.5 mm
2
/16 AWG
Maximum cross-section to control terminals, flexible wire with cable end sleeves
1 mm
2
/18 AWG
Maximum cross-section to control terminals, flexible wire with cable end sleeves with collar
0.5 mm
2
/20 AWG
Minimum cross-section to control terminals
0.25 mm
2
/24 AWG
1)
For power cables, see chapter 4.1 Electrical Data, 380–500 V.
Selection
Design Guide
78