FC 302
P630
P710
P800
High/Normal load*
HO
NO
HO
NO
HO
NO
Typical shaft output at 550 V [kW]
500
560
560
670
670
750
Typical shaft output at 575 V [HP]
650
750
750
950
950
1050
Typical shaft output at 690 V [kW]
630
710
710
800
800
900
Enclosure IP21, IP54 without/with options
cabinet
F1/ F3
F1/ F3
F1/ F3
Output current
Continuous (at 550 V) [A]
659
763
763
889
889
988
Intermittent (60 s overload) (at 550 V) [A]
989
839
1145
978
1334
1087
Continuous (at 575/690 V) [A]
630
730
730
850
850
945
Intermittent (60 s overload) (at 575/690 V) [A]
945
803
1095
935
1275
1040
Continuous KVA (at 550 V) [KVA]
628
727
727
847
847
941
Continuous KVA (at 575 V) [KVA]
627
727
727
847
847
941
Continuous KVA (at 690 V) [KVA]
753
872
872
1016
1016
1129
Maximum input current
Continuous (at 550 V) [A]
642
743
743
866
866
962
Continuous (at 575 V) [A]
613
711
711
828
828
920
Continuous (at 690 V) [A]
613
711
711
828
828
920
Max. cable size, motor [mm
2
(AWG)
1)
]
8x150 (8x300 mcm)
Max. cable size, line power F1 [mm
2
(AWG)
1)
]
8x240 (8x500 mcm)
Max. cable size, line power F3 [mm
2
(AWG)
1)
]
8x456 (8x900 mcm)
Max. cable size, load sharing [mm
2
(AWG)
1)
]
4x120 (4x250 mcm)
Max. cable size, brake [mm
2
(AWG)
1)
]
4x185 (4x350 mcm)
Max. external electrical fuses [A]
2)
1600
Estimated power loss at 600 V [W]
3)
4)
8075
9500
9165
10872
10860
12316
Estimated power loss at 690 V [W]
3)
4)
8388
9863
9537
11304
11291
12798
F3/F4 Max added losses CB or disconnect &
contactor
342
427
419
532
519
615
Max panel options losses
400
Weight, enclosure IP21, IP54 [kg]
1017/1318
Weight, rectifier module [kg]
102
102
102
Weight, inverter module [kg]
102
102
136
Efficiency
4)
0.98
Output frequency
0–500 Hz
Heatsink overtemp. trip
203 °F [95 °C]
221 °F [105 °C]
203 °F [95 °C]
Power card ambient trip
185 °F [85 °C]
* High overload=160% torque during 60 s, Normal overload=110% torque during 60 s.
Table 4.10 Technical Specifications, F1/F3 frames, 525–690 V Line Power Supply 3x525–690 V AC
1) American Wire Gauge.
2) For fuse ratings, see chapter 7.2.1 Fuses.
3) Typical power loss is at normal conditions and expected to be within
±
15% (tolerance relates to variety in voltage and cable conditions.) These
values are based on a typical motor efficiency (IE/IE3 border line). Lower efficiency motors add to the power loss in the adjustable frequency drive.
If the switching frequency is raised from nominal, the power losses rise significantly. LCP and typical control card power consumptions are
included. Options and customer load can add up to 30 W to the losses, though usually a fully loaded control card and options for slots A and B
each add only 4 W.
4) Measured using 16.5 ft. [5 m] shielded motor cables at rated load and rated frequency.
Selection
Design Guide
MG34S222
Danfoss A/S © Rev. 2014-02-10 All rights reserved.
73
4
4