4.2.1 Electrical Data, 525–690 V AC, 12-Pulse
FC 302
P355
P400
P500
P560
High/Normal load
HO
NO
HO
NO
HO
NO
HO
NO
Typical shaft output at 550 V [kW]
315
355
315
400
400
450
450
500
Typical shaft output at 575 V [HP]
400
450
400
500
500
600
600
650
Typical shaft output at 690 V [kW]
355
450
400
500
500
560
560
630
Enclosure IP21
F8/F9
F8/F9
F8/F9
F8/F9
Enclosure IP54
F8/F9
F8/F9
F8/F9
F8/F9
Output current
Continuous (at 550 V) [A]
395
470
429
523
523
596
596
630
Intermittent (60 s overload)
(at 550 V) [A]
593
517
644
575
785
656
894
693
Continuous (at 575/690 V) [A]
380
450
410
500
500
570
570
630
Intermittent (60 s overload) (at
575/690 V) [A]
570
495
615
550
750
627
855
693
Continuous KVA (at 550 V) [KVA]
376
448
409
498
498
568
568
600
Continuous KVA (at 575 V) [KVA]
378
448
408
498
498
568
568
627
Continuous KVA (at 690 V) [KVA]
454
538
490
598
598
681
681
753
Maximum input current
Continuous (at 550 V) [A]
381
453
413
504
504
574
574
607
Continuous (at 575 V) [A]
366
434
395
482
482
549
549
607
Continuous (at 690 V) [A]
366
434
395
482
482
549
549
607
Max. cable size, line power
[mm
2
(AWG)
1)
]
4x85 (3/0)
Max. cable size, motor
[mm
2
(AWG)
1)
]
4x250 (500 mcm)
Max. cable size, brake
[mm
2
(AWG)
1)
]
2x185 (2x350 mcm)
2x185 (2x350 mcm)
2x185 (2x350 mcm)
2x185 (2x350 mcm)
Max. external electrical fuses [A]
2)
630
Estimated power loss at
600 V [W]
3)
4)
4424
5323
4795
6010
6493
7395
7383
8209
Estimated power loss at
690 V [W]
3)
4)
4589
5529
4970
6239
6707
7653
7633
8495
Weight, enclosure IP21, IP54 [kg]
447/669
Efficiency
4)
0.98
Output frequency
0–500 Hz
Heatsink overtemp. trip
230 °F [110 °C]
Power card ambient trip
185 °F [85 °C]
* High overload=160% torque during 60 s, Normal overload=110% torque during 60 s.
Table 4.12 Technical Specifications F8/F9 frames, 525–690 V Line Power Supply 6x525–690 V AC, 12-Pulse
1) American Wire Gauge.
2) For fuse ratings, see chapter 7.2.1 Fuses.
3) Typical power loss is at normal conditions and expected to be within
±
15% (tolerance relates to variety in voltage and cable conditions.) These
values are based on a typical motor efficiency (IE/IE3 border line). Lower efficiency motors add to the power loss in the adjustable frequency drive.
If the switching frequency is raised from nominal, the power losses rise significantly. LCP and typical control card power consumptions are
included. Options and customer load can add up to 30 W to the losses, though usually a fully loaded control card and options for slots A and B
each add only 4 W.
4) Measured using 16.5 ft. [5 m] shielded motor cables at rated load and rated frequency.