Input Polarity of Control Terminals
12
13
18
19
27
29
32
33
20
37
+24
V DC
0
VDC
130
BT106.10
PNP (Source)
Digital input wiring
Figure 7.50 Input Polarity of Control Terminals
NPN (Sink)
Digital input wiring
12
13
18
19
27
29
32
33
20
37
+24
V DC
0
VDC
130
BT107.11
Figure 7.51 Input Polarity of Control Terminals
7.5.9 Relay Output D Frame
Relay 1
•
Terminal 01: common
•
Terminal 02: normally open 400 V AC
•
Terminal 03: normally closed 240 V AC
Relay 2
•
Terminal 04: common
•
Terminal 05: normally open 400 V AC
•
Terminal 06: normally closed 240 V AC
Relay 1 and relay 2 are programmed in
5-40 Function Relay
,
5-41 On Delay, Relay
, and
5-42 Off Delay, Relay
.
Use option module MCB 105 for additional relay outputs.
130BC554.10
relay1
relay2
03
02
240Vac, 2A
01
06
05
04
240Vac, 2A
400Vac, 2A
400Vac, 2A
Figure 7.52 D-Frame Additional Relay Outputs
7.5.10 Relay Output E & F-Frame
Relay 1
•
Terminal 01: common
•
Terminal 02: normally open 240 V AC
•
Terminal 03: normally closed 240 V AC
Relay 2
•
Terminal 04: common
•
Terminal 05: normally open 400 V AC
•
Terminal 06: normally closed 240 V AC
Relay 1 and relay 2 are programmed in
5-40 Function Relay
,
5-41 On Delay, Relay
, and
5-42 Off Delay, Relay
.
Use option module MCB 105 for additional relay outputs.
Electrical Installation
Design Guide
MG34S222
Danfoss A/S © Rev. 2014-02-10 All rights reserved.
231
7
7