Frame size
Bussmann PN
Rating
Alternative fuses
F8-F13
LPJ-6 SP or SPI
6 A, 600 V
Any listed Class J Dual Element,
Time Delay, 6 A
Table 7.55 Control Transformer Fuse
Frame size
Bussmann PN
Rating
F8-F13
GMC-800 MA
800 mA, 250 V
Table 7.56 NAMUR Fuse
Frame size
Bussmann PN
Rating
Alternative fuses
F8-F13
LP-CC-6
6 A, 600 V
Any listed Class CC, 6 A
Table 7.57 Safety Relay Coil Fuse with Pilz Relay
Frame
size
Power & Voltage
Type
Default breaker settings
Trip level [A]
Time [s]
F3
P450 380–500 V & P630-P710
525–690 V
Merlin Gerin
NPJF36120U31AABSCYP
1200
0.5
F3
P500-P630 380–500 V & P800
525–690 V
Merlin Gerin
NRJF36200U31AABSCYP
2000
0.5
F4
P710 380–500 V & P900-P1M2
525–690 V
Merlin Gerin
NRJF36200U31AABSCYP
2000
0.5
F4
P800 380–500 V
Merlin Gerin
NRJF36250U31AABSCYP
2500
0.5
Table 7.58 F-frame Circuit Breakers
7.3 Disconnectors and Contactors
7.3.1 Line Power Disconnects - Frame Sizes E and F
Frame size
Power
Type
380–500 V
D5h/D6h
N55K–N132
ABB OT400U03
D7h/D8h
N160–N315
ABB OT600U03
E1/E2
P250
ABB OETL-NF600A
E1/E2
P315–P400
ABB OETL-NF800A
F3
P450
Merlin Gerin NPJF36000S12AAYP
F3
P500–P630
Merlin Gerin NRKF36000S20AAYP
F4
P710–P800
Merlin Gerin NRKF36000S20AAYP
525–690 V
D5h/D6h
N90K–N132
ABB OT400U03
D7h/D8h
N160–N250
ABB OT600U03
E1/E2
P355–P560
ABB OETL-NF600A
F3
P630–P710
Merlin Gerin NPJF36000S12AAYP
F3
P800
Merlin Gerin NRKF36000S20AAYP
F4
P900–P1M2
Merlin Gerin NRKF36000S20AAYP
Table 7.59 Line Power Disconnects, 6-Pulse Adjustable Frequency Drives
Electrical Installation
Design Guide
MG34S222
Danfoss A/S © Rev. 2014-02-10 All rights reserved.
217
7
7
Содержание VLT AutomationDrive FC 300
Страница 2: ......