130BB256.10
Figure 7.39 Shield Termination/Strain Relief for Serial
Communication Bus Conductors
Installation of 24 V External DC Supply
Torque: 0.5
‒
0.6 Nm (5 in-lbs)
Screw size: M3
24 V DC external supply can be used as a low-voltage
supply to the control card and any installed option cards.
This enables full operation of the LCP (including parameter
setting) without connection to line power. Note that a
warning of low voltage displays when 24 V DC has been
connected; however, there is no tripping.
No.
Function
35 (-), 36 (+)
24 V external DC supply
Table 7.67 Terminal Numbers for External 24 V Supply
WARNING
Use a 24 V DC supply of type PELV to ensure correct
galvanic isolation (type PELV) on the control terminals of
the adjustable frequency drive.
7.5.3 Control Terminals
Drawing Reference Numbers:
1.
10-pole plug digital I/O
2.
3-pole plug RS-485 Bus
3.
6-pole analog I/O
4.
USB Connection
1
4
2
3
130BA012.12
61
68
69
39
42
50
53
54
55
12
13
18
19
27
29
32
33
20
37
Figure 7.40 Control Terminals (All Frame Sizes)
7.5.4 Switches S201 (A53), S202 (A54), and
S801
Switches S201 (A53) and S202 (A54) are used to select a
current (0–20 mA) or a voltage (-10 to +10 V) configuration
of the analog input terminals 53 and 54 respectively.
Switch S801 (BUS TER.) can be used to enable termination
on the RS-485 port (terminals 68 and 69). See
Default Setting:
S201 (A53)=OFF (voltage input)
S202 (A54)=OFF (voltage input)
S801 (Bus termination)=OFF
Electrical Installation
Design Guide
224
Danfoss A/S © Rev. 2014-02-10 All rights reserved.
MG34S222
7
7
Содержание VLT AutomationDrive FC 300
Страница 2: ......