![background image](http://html1.mh-extra.com/html/danfoss/vlt-aqua/vlt-aqua_instruction-manual_3483148038.webp)
5.1.15 Motor connection for B1 and B2
Figure 5.23: First terminate the motor ground, then place motor U, V and W wires in the terminal and tighten them. Please ensure that the
outer insulation of the motor cable is removed under the EMC clamp.
5.1.16 Motor connection for B3 and B4
Figure 5.24: First terminate the motor ground, then place
motor U, V and W wires in the terminal and tighten them.
Please ensure that the outer insulation of the motor cable is
removed under the EMC clamp.
Figure 5.25: First terminate the motor ground, then place
motor U, V and W wires in the terminal and tighten them.
Please ensure that the outer insulation of the motor cable is
removed under the EMC clamp.
5 Electrical installation
VLT
®
AQUA Drive
Instruction Manual
5-16
MG.20.M5.22 - VLT
®
is a registered Danfoss trademark
5