EXAMPLE 3:
Variable value= REFERENCE, range= Min ref - Max ref
Range needed for output= Min ref (0%) - Max ref (100%), 0–10 mA
Output signal 0 or 4 mA is needed at Min ref - set par.6-51
Terminal 42 Output Min Scale
to 0%
Output signal 10 mA is needed at Max ref (100% of range) - set par.6-52
Terminal 42 Output Max Scale
to 200%
(20 mA / 10 mA x 100%=200%).
8.2.9 Drive Closed-loop, 20-**
This parameter group is used for configuring the closed-loop PID controller, which controls the output frequency of the adjustable frequency drive.
20-12 Reference/Feedback Unit
Option:
Function:
[0]
None
[1] *
%
[5]
PPM
[10]
1/min
[11]
RPM
[12]
Pulse/s
[20]
l/s
[21]
l/min
[22]
l/h
[23]
m
3
/s
[24]
m
3
/min
[25]
m
3
/h
[30]
kg/s
[31]
kg/min
[32]
kg/h
[33]
t/min
[34]
t/h
[40]
m/s
[41]
m/min
[45]
m
VLT
®
AQUA Drive
Instruction Manual
8 How to program the adjustable frequency
drive
MG.20.M5.22 - VLT
®
is a registered Danfoss trademark
8-33
8