Enclosure
At reduced fan speed (50%)
[dBA] ***
Full fan speed
[dBA]
A2
51
60
A3
51
60
A5
54
63
B1
61
67
B2
58
70
B3
-
-
B4
-
-
C1
52
62
C2
55
65
C3
-
-
C4
-
-
D1+D3
74
76
D2+D4
73
74
E1/E2 *
73
74
E1/E2 **
82
83
* 450 hp [315 kW], 380–480 V AC and 500 hp [355 kW], 525–600 V AC only!
** Remaining E1+E2 power sizes.
*** For D and E sizes, reduced fan speed is at 87%, measured at 200 V.
When a transistor in the inverter bridge switches, the voltage across the motor increases by a du/dt ratio depending on:
-
the motor cable (type, cross-section, length, shielded or unshielded)
-
inductance
The natural induction causes an overshoot U
PEAK
in the motor voltage before it stabilizes itself at a level depending on the voltage in the intermediate
circuit. The rise time and the peak voltage U
PEAK
affect the service life of the motor. If the peak voltage is too high, motors without phase coil insulation
are especially affected. If the motor cable is short (by a few yards), the rise time and peak voltage are lower.
If the motor cable is long (328 ft [100 m]), the rise time and peak voltage are higher.
In motors without phase insulation paper or other insulation reinforcement suitable for operation with voltage supply (such as an adjustable frequency
drive), fit a du/dt filter or a sine-wave filter on the output of the adjustable frequency drive.
10 Specifications
VLT
®
AQUA Drive
Instruction Manual
10-16
MG.20.M5.22 - VLT
®
is a registered Danfoss trademark
10
Содержание vlt aqua
Страница 4: ...Contents VLT AQUA Drive Instruction Manual MG 20 M5 22 VLT is a registered Danfoss trademark...
Страница 12: ...2 Safety VLT AQUA Drive Instruction Manual 2 6 MG 20 M5 22 VLT is a registered Danfoss trademark 2...
Страница 16: ...3 Introduction VLT AQUA Drive Instruction Manual 3 4 MG 20 M5 22 VLT is a registered Danfoss trademark 3...