29-04 Pipe Fill Rate
Range:
Function:
0.001 units/
s*
[0.001–999999.999 units/s]
Specifies the filling rate in units/second using the PI controller. Filling rate units are feedback units/
second. This function is used for filling vertical pipe systems but will be active when the filling time
has expired, no matter what, until the pipe fill setpoint set in par. 29-05 is reached.
29-05 Filled Setpoint
Range:
Function:
0 s*
[0–999999,999 s]
Specifies the filled setpoint at which the pipe fill function will be disabled and the PID controller will
take control. This function can be used both for horizontal and vertical pipe systems.
8.3 Parameter Options
8.3.1 Default settings
Changes during operation:
“TRUE” means that the parameter can be changed while the adjustable frequency drive is in operation, and “FALSE” means that the adjustable frequency
drive must be stopped before a change can be made.
4 set-up:
'All set-up': the parameter can be set individually in each of the four set-ups, i. e., one single parameter can have four different data values.
’1 set-up’: data value will be the same in all set-ups.
SR:
Size related
N/A:
No default value available.
Conversion index:
This number refers to a conversion figure used when writing or reading by means of an adjustable frequency drive.
Conv. index
100
67
6
5
4
3
2
1
0
-1
-2
-3
-4
-5
-6
Conv. factor
1
1/60
1000000
100000
10000
1000
100
10
1
0.1
0.01
0.001
0.0001
0.00001
0.000001
Data type
Description
Type
2
Integer 8
Int8
3
Integer 16
Int16
4
Integer 32
Int32
5
Unsigned 8
Uint8
6
Unsigned 16
Uint16
7
Unsigned 32
Uint32
9
Visible String
VisStr
33
Normalized value 2 bytes
N2
35
Bit sequence of 16 Boolean variables
V2
54
Time difference w/out date
TimD
VLT
®
AQUA Drive
Instruction Manual
8 How to program the adjustable frequency
drive
MG.20.M5.22 - VLT
®
is a registered Danfoss trademark
8-47
8
Содержание vlt aqua
Страница 4: ...Contents VLT AQUA Drive Instruction Manual MG 20 M5 22 VLT is a registered Danfoss trademark...
Страница 12: ...2 Safety VLT AQUA Drive Instruction Manual 2 6 MG 20 M5 22 VLT is a registered Danfoss trademark 2...
Страница 16: ...3 Introduction VLT AQUA Drive Instruction Manual 3 4 MG 20 M5 22 VLT is a registered Danfoss trademark 3...