[120]
Lead Pump Start
[121]
Lead Pump Alternation
[130]
Pump 1 Interlock
[131]
Pump 2 Interlock
[132]
Pump 3 Interlock
8-13 Configurable Status Word STW
Option:
Function:
This parameter enables configuration of bits 12 – 15 in the status word.
[0]
No function
[1] *
Profile Default
Function corresponds to the profile default selected in par. 8-10
Control Profile
.
[2]
Alarm 68 Only
Only set in case of an Alarm 68.
[3]
Trip excl Alarm 68
Set in case of a trip, except if the trip is executed by an Alarm 68.
[16]
T37 DI status
The bit indicates the status of terminal 37.
“0” indicates T37 is low (safe stop)
“1” indicates T37 is high (normal)
5-40 Function Relay
Array [8]
(Relay 1 [0], Relay 2 [1], Relay 7 [6], Relay 8 [7], Relay 9 [8])
Select options to define the function of the relays.
The selection of each mechanical relay is realized in an array parameter.
[0]
No Operation
[1]
Control Ready
[2]
Drive Ready
[3]
Drive Ready/Remote
[4]
Stand-by/No Warning
[5] *
Running
[6]
Running/No Warning
[8]
Run on Ref./No Warning
[9]
Alarm
[10]
Alarm or Warning
[11]
At Torque Limit
[12]
Out of Current Range
[13]
Below Current, low
[14]
Above Current, high
[15]
Out of Speed Range
[16]
Below Speed, low
[17]
Above Speed, high
[18]
Out of Feedb. Range
[19]
Below Feedback, low
[20]
Above Feedback, high
[21]
Thermal Warning
8 How to program the adjustable frequency
drive
VLT
®
AQUA Drive
Instruction Manual
8-26
MG.20.M5.22 - VLT
®
is a registered Danfoss trademark