22-33 Low Speed [Hz]
Range:
Function:
0 Hz*
[0.0 - par. 22-37 Hz]
To be used if par. 0-02
Motor Speed Unit
has been set for Hz (parameter not visible if RPM selected).
Set used speed to the 50% level.
The function is used for storing values needed to tune No-flow Detection.
22-34 Low Speed Power [kW]
Range:
Function:
0 kW*
[0.00 - 0.00 kW]
To be used if par. 0-03
Regional Settings
has been set for International (parameter not visible if
North America selected).
Set power consumption to 50% speed level.
This function is used for storing values needed to tune No-flow Detection.
22-35 Low Speed Power [HP]
Range:
Function:
0 hp*
[0.00 - 0.00 hp]
To be used if par. 0-03
Regional Settings
has been set for North America (parameter not visible if
International selected).
Set power consumption to 50% speed level.
This function is used for storing values needed to tune No-flow Detection.
22-36 High Speed [RPM]
Range:
Function:
0 RPM*
[0 - par. 4-13 RPM]
To be used if par. 0-02
Motor Speed Unit
has been set for RPM (parameter not visible if Hz selected).
Set used speed for the 85% level.
The function is used for storing values needed to tune No-flow Detection.
22-37 High Speed [Hz]
Range:
Function:
0.0 Hz*
[0.0 - par. 4-14 Hz]
To be used if par. 0-02
Motor Speed Unit
has been set for Hz (parameter not visible if RPM selected).
Set used speed for the 85% level.
The function is used for storing values needed to tune No-flow Detection.
22-38 High Speed Power [kW]
Range:
Function:
0 kW*
[0.00 - 0.00 kW]
To be used if par. 0-03
Regional Settings
has been set for International (parameter not visible if
North America selected).
Set power consumption to 85% speed level.
This function is used for storing values needed to tune No-flow Detection.
22-39 High Speed Power [HP]
Range:
Function:
0 hp*
[0.00 - 0.00 hp]
To be used if par. 0-03
Regional Settings
has been set for North America (parameter not visible if
International selected).
Set power consumption to 85% speed level.
This function is used for storing values needed to tune No-flow Detection.
22-40 Minimum Run Time
Range:
Function:
10 s*
[0 - 600 s]
Set the desired minimum running time for the motor after a start command (digital input or bus)
before entering sleep mode.
8 How to program the adjustable frequency
drive
VLT
®
AQUA Drive
Instruction Manual
8-38
MG.20.M5.22 - VLT
®
is a registered Danfoss trademark
8
Содержание vlt aqua
Страница 4: ...Contents VLT AQUA Drive Instruction Manual MG 20 M5 22 VLT is a registered Danfoss trademark...
Страница 12: ...2 Safety VLT AQUA Drive Instruction Manual 2 6 MG 20 M5 22 VLT is a registered Danfoss trademark 2...
Страница 16: ...3 Introduction VLT AQUA Drive Instruction Manual 3 4 MG 20 M5 22 VLT is a registered Danfoss trademark 3...