48 · vacon
Parameter list
Tel. +358 (0)201 2121 • Fax: +358 (0)201 2121 205
4
4.9
Protections
4.9.1
General
Table 29.
Protections, G2.9
Code
Parameter
Min
Max
Uni
t
Default
ID
Description
P2.9.1.1
Thermistor Fault
Response
0
3
2 / Fault
732
0 = No response
1 = Warning
2 = Fault, stop acc. stop
mode
3 = Fault, stop by coasting
P2.9.1.2
Overtemperature
Response
2
5
2 / Fault
1757
As Par. P2.9.1.4
P2.9.1.3
Overvoltage Response
2
5
2 / Fault
1755
As Par. P2.9.1.4
P2.9.1.4
Cooling Flt. Delay
0
7
s
2
751
P2.9.1.5 LCL
Overtemperature 0
3
2
1505
P2.9.1.6 Max
Charge
Time 0.00
30.00
s 5.00 1522
Charging time limit when
drive charging options are
used.
P2.9.1.7
MCB At Fault
0
1
0
1699
0 = No Action
1 = Open MCB
P2.9.1.8
Start Fault Delay
0.00
320.00
s
3.00
1512
P2.9.1.9
Quick Stop Response
1
2
1 / Warning
1758
1 = Warning
2 = Fault
P2.9.1.10
Reactive Error Trip
Limit
-300 300 %
7.5
1759
P2.9.1.11
MCB Fault Delay
0.00
10.00
s
3.50
1521
P2.9.1.12
Line Phase Supervision
0
2
0 / No Action
702
0 = No Action
1 = Warning
2 = Fault
P2.9.1.13
4 mA Fault Response
0
2
0 / No Action
700
0 = No Action
1 = Warning
2 = Fault
P2.9.1.14
Reactive Current Limit
Response
0
2
1 / Warning
1981
0 = No Action
1 = Warning
2 = Fault
4.9.2
PT-100
Table 30.
Code
Parameter
Min
Max
Unit
Default
ID
Description
P2.9.2.1 PT100
Numbers 0 5
0
739
0 = Not used (ID Write)
1 = PT100 input 1
2 = PT100 input 1 & 2
3 = PT100 input 1 & 2 & 3
2 = PT100 input 2 & 3
3 = PT100 input 3
P2.9.2.2
PT100 FaultResponse
0
3
2 / Fault
740
0 = No response
1 = Warning
2 = Fault,stop acc. to 2.4.7
3 = Fault,stop by coasting
P2.9.2.3 PT100
Warn.Limit -30
200
°C
120
741
P2.9.2.4
PT100 Fault Lim.
-30
200
°C
130
742
P2.9.2.5
PT100 2 Inputs
0
5
0
743
See
ID739
P2.9.2.6
PT100 2 WarnLim
-30
200
°C
120
745
P2.9.2.7
PT100 2 FaultLim
-30
200
°C
130
746