Parameter list
vacon · 41
24-hour support: +358 (0)201 212 575 • Email: [email protected]
4
4.4.6
Analogue input 4
Table 14.
Analogue Input 2, G2.2.3
Code
Parameter
Min
Max
Unit
Default
ID
Description
P2.4.6.1
AI4 signal selection
0.1
E.10
0.1
152
P2.4.6.2
AI4 filter time
0.000
32.000
s
0.000
153
P2.4.6.3
AI4 custom
minimum setting
-160.00 160.00 %
0.00
155
P2.4.6.4
AI4 custom
maximum setting
-160.00 160.00 %
100.00
156
P2.4.6.5
AI4 signal inversion
0
1
0
162
P2.4.6.6
AI4 reference
scaling, minimum
value
-32000 32000
0
1039
P2.4.6.7
AI4 reference
scaling, maximum
value
-32000 32000
0
1040
P2.4.6.8
AI4 Controlled ID
0
10000
0
1510
4.5
Output signals
4.5.1
Digital output signals
Table 15.
Digital output signals, G2.3.1
Code
Parameter
Min
Max
Unit
Default
ID
Description
P2.5.1.1
MCB1 Close Control
0.1
E.10
0.1
1218
AFE contactor, fixed to relay
output B.2
P2.5.1.2
MCB1 Open Control
0.1
E.10
0.1
1219
P2.5.1.3
Ready 0.1
E.10
0.1
432
The AC drive is ready to
operate.
P2.5.1.4
Run 0.1
E.10
0.1
433
The AC drive operates (the
motor is running).
P2.5.1.5
Common Fault
0.1
E.10
0.1
434
A fault trip has occurred.
P2.5.1.6
Fault, Inverted
0.1
E.10
0.1
435
No fault trip has occurred.
P2.5.1.7
At reference
0.1
E.10
0.1
442
P2.5.1.8
Overtemperature
Warn.
0.1 E.10
0.1
439
The heatsink temperature
e70 °C
P2.5.1.9
Warning
0.1
E.10
0.1
436
General warning signal.
P2.5.1.10
CB2 Close Control
0.1
E.10
0.1
1709
Second AFE contactor
control
P2.5.1.11
NET Contactor
0.1
E.10
0.1
1605
NET contactor ( DC )
P2.5.1.12 D7
Synchronized 0.1
E.10
0.1
1753
Drive is synchronised to D7
card
P2.5.1.13 Charge
Control 0.1
E.10
0.1 1568
Charge control from start
command
P2.5.1.14 Common
Alarm 0.1
E.10
0.1
1684
P2.5.1.15
Ready For Start
0.1
E.10
0.1
1686
No conditions that could
disable starting active
P2.5.1.16
Quick Stop Active
0.1
E.10
0.1
1687
P2.5.1.17
Fieldbus digital input 1
0.1
0.1
0.1
455
FB CW B11
P2.5.1.18
FB Dig 1 Parameter
ID0
ID0
891
Select parameter to control
P2.5.1.19
Fieldbus digital input 2
0.1
0.1
0.1
456
FB CW B12
P2.5.1.20
FB Dig 2 Parameter
ID0
ID0
892
Select parameter to control
P2.5.1.21
Fieldbus digital input 3
0.1
0.1
0.1
457
FB CW B13
P2.5.1.22
FB Dig 3 Parameter
ID0
ID0
893
Select parameter to control
P2.5.1.23
Fieldbus digital input 4
0.1
0.1
0.1
169
FB CW B14
P2.5.1.24
FB Dig 4 Parameter
ID0
ID0
894
Select parameter to control