22 · vacon
Monitoring signals
Tel. +358 (0)201 2121 • Fax: +358 (0)201 2121 205
3
3.2
Description of monitoring values
3.2.1
Monitoring 1 values
V1.1.1 DC-Link
Voltage
V ID1108
The measured DC voltage, filtered.
V1.1.2 DC
Voltage
Ref.
% ID1200
The DC voltage reference. Compared to given supply voltage.
DC Voltage = Grid Nom Voltage (P2.1.1) * 1.35 * DC Voltage Ref.
1025 Vdc
690 Vac ∗ 1,35 ∗ 1,10
V1.1.3 DC
Voltage
Act.
% ID7
The actual DC Voltage, measured DC Voltage scaled to % value.
DC Voltage Act. = DC Voltage * 100 / (
Grid Nom Voltage (P2.1.1) * 1.35)
110,00 %
1025 Vdc ∗ 100 / 690 ∗ 1,35
V1.1.4
Total Current
A
ID 1113
The filtered current of the drive.
V1.1.5
Active Current %
ID 1125
The active current in % of System Rated Current.
A negative value means that the current is flowing to AC side from DC side.
V1.1.6
Reactive Current
%
ID 1157
The reactive current of the regenerative drive in % of System Rated Current.
V1.1.7
Power kW
kW
ID 1508
The output power of the drive in kW.
A negative value means that the current is flowing to AC side from DC side.
V1.1.8 Power
%
% ID
5
The output power of the drive in %. 100,0 % eguals 100.0 % Active Current and 100.0 %
Supply Voltage.
A negative value means that the current is flowing to AC side from DC side.