Monitoring signals
vacon · 25
24-hour support: +358 (0)201 212 575 • Email: [email protected]
3
V1.2.7 Frequency
Reference
Hz ID1752
The used frequency reference. In AFE mode, the frequency reference is determined
internally when the synchronisation is made. In Island and Micro Grid mode, the
reference is used for a static power supply, and a power drooping in Micro Grid mode.
V1.2.8 Current
A ID
1113
The unfiltered current of the drive.
V1.2.9
SG Synch Error ID1658
A synchronisation error to the shaft generator frequency.
V1.2.10 Operation
Hours
h ID1856
This shows operation hours of the drive. G2.7 Operation Time is used to enter old value if
the software is updated.
V1.2.11
Reactive Current Reference
%
ID1389
The final reactive current reference.
V1.2.12 Grid
State
ID1882
The Status Word for the grid.
Grid State ID1882
b0
Supply frequency or frequency from OPT-D7 below fault limit
b1
Supply frequency or frequency from OPT-D7 below warning limit
b2
Supply frequency or frequency from OPT-D7 above warning limit
b3
Supply frequency or frequency from OPT-D7 above fault limit
b4
Voltage from OPT-D7 below fault limit
b5
Voltage from OPT-D7 below warning limit
b6
Voltage from OPT-D7 above warning limit
b7
Voltage from OPT-D7 above fault limit
b8
Supply voltage below fault limit
b9
Supply voltage below warning limit
b10
Supply voltage above warning limit
b11
Supply voltage above fault limit
b12
b13
b14
b15
V1.2.13 Mindex
% ID1874
This value can be used to recognize low Dc-Link voltage when operating in island and
uGrid modes. If the value is above 90%, the drive is in limits to make correct voltage to
the AC side.