Description of parameters
vacon · 105
24-hour support: +358 (0)201 212 575 • Email: [email protected]
5
2.10.23
SW ID.Bit selection B11
ID1907
2.10.24
SW ID.Bit selection B12
ID1908
2.10.25
SW ID.Bit selection B13
ID1909
2.10.26
SW ID.Bit selection B14
ID1910
Select the bit that used in FB Status Word Bit 11, 12, 13 and 14.
2.10.27
uGrid CW B12 parameter ID891
“uCW
B12”
2.10.28
uGrid CW B13 parameter
ID892 “uCW B13”
2.10.29
uGrid CW B14 parameter
ID893 “uCW B14”
2.10.30
uGrid CW B15 parameter
ID894 “uCW B15”
With these parameters you can define the parameter to be controlled by using Micro Grid
Control Word bits 12-15.
5.11
Micro Grid
2.11.1 Control
Mode
Select the AFE operation mode.
0 = AFE
Standard AFE functionality, no license key required. Keeps fixed DC-Link Voltage.
1 = Island
Island operation mode, cannot operate parallel with other power sources. Makes fixed
voltage and frequency, i.e. no voltage or frequency drooping. Also low DC-Link Voltage
limitation function is disabled. Reacts only to set DC Under Voltage limit.
2 = Micro Grid
uGrid operation mode, can operate parallel with other power sources. Parallel operation
is achieved by voltage and frequency drooping. Start to reduce output frequency when
not sufficient DC-Link Voltage, this will prevent reactive current generation in case of
low power in DC-Link side.
3 = Island-AFE
The drive changes the control mode automatically when feedback from the external net
contactor has been received.
4 = Island-Micro Grid
The drive changes the control mode automatically when feedback from the external net
contactor has been received.
5 = (Reserved)
6 = Free Select
The operation mode is selected by digital inputs and AFE mode 1-3 selections.
NOTE! A licence is necessary for other than the standard AFE mode.