Monitoring signals
vacon · 23
24-hour support: +358 (0)201 212 575 • Email: [email protected]
3
V1.1.9
Status Word (Application)
ID 43
The Application Status Word combines different statuses of the drive to one data word.
Status Word (Application) ID43
FALSE
TRUE
b0
b1
Not in Ready state
Ready
b2 Not
Running
Running
b3 No
Fault
Fault
b4
b5
Quick stop active
Quick stop not active
b6
Run Disabled
Run Enable
b7 No
Warning
Warning
b8
Charging Switch closed (internal)
b9
MCB Control
b10
MCB Feedback
b11
b12
No Run Request
Run Request
b13
At Current Limit
b14
Island Mode Active
b15
uGrid Mode Active
V1.1.10
Supply Frequency
Hz
ID 1
The drive output frequency. Updated in the STOP state when Regen Option B9 is
activated.
V1.1.11
Supply Voltage V
ID 1107
The drive output voltage.
V1.1.12
Line Frequency D7
Hz
ID 1654
The measured line voltage frequency when using the OPT-D7 option board in slot C.
When the OPT-D7 board is not used, it is possible to use Analogue Input 3 and 4 ID write
function to give the grid the Line Frequency and Line Voltage. This enables use of grid PI
voltage controller without the OPT-D7 board. Note that both line frequency and line
voltages needs to be given. By activating Control Options 2 B2 these analogue inputs can
be used also to grid protection.
V1.1.13
Line Voltage D7 V
ID 1650
The measured line voltage rms value when using the OPT-D7 option board in slot C.
When the OPT-D7 board is not used, it is possible to use Analogue Input 3 and 4 ID write
function to give the grid the Line Frequency and Line Voltage. This enables use of grid PI
voltage controller without the OPT-D7 board. Note that both line frequency and line
voltages needs to be given. By activating Control Options 2 B2 these analogue inputs can
be used also to grid protection.