Description of parameters
vacon · 73
24-hour support: +358 (0)201 212 575 • Email: [email protected]
5
AI3/AI4 Output
Analogue
Input
100 %
0 %
0 %
100 %
40 %
Custom
Min
80 %
Custom
Max
Figure 21.
2.4.3.5
AI1 signal inversion
ID387 “AI1 Signal Inv”
2.4.4.5
AI2 signal inversion
ID398 “AI2 Signal Inv”
2.4.5.5
AI3 signal inversion
ID151 “AI3 Signal Inv”
2.4.6.5
AI4 signal inversion
ID162 “AI3 Signal Inv”
The signal inversion function is useful for example in a situation where PLC sends power
limit to the drive by using analogue inputs. If PLC is unable to communicate to the drive,
the power limit is normally zero. When an inverted signal logic is used, a zero value from
PLC means maximum power limit. This allows you to run the drive, for example, from
the keypad without changing the power limit parameters.
0 = No inversion
1 = Signal inverted
AI3/AI4 Output
Analogue
Input
100 %
0 %
40 %
Custom
Min
80 %
Custom
Max
Figure 22.