66 · vacon
Description of parameters
Tel. +358 (0)201 2121 • Fax: +358 (0)201 2121 205
5
Together with inductor size and inductor losses voltage will be increased
18 Vac + 4,5 Vac = 22,5 Vac from Supply Voltage parameter -> 422,5 Vac.
2.2.6.7 Voltage
Down (DigIn)
ID1551
Select a digital input to decrease the supply voltage with a set ramp rate.
2.2.6.8 Voltage
Up
(DigIn) ID1550
Select a digital input to increase the supply voltage with a set ramp rate.
2.2.6.9
Voltage Adjust Rate
ID1555
Defines the rate that is used to change the base voltage when Up and Down inputs are
used.
2.2.6.10
Voltage Maximum Adjust
ID1639
The maximum adjustment to the voltage when controlling reactive power.
5.3
Ramp control
P2.3.1 Ramp
Time ID103
This parameter defines the time required for the frequency to increase and decrease
between zero frequency and P2.3.2 Ramp Range.
P2.3.2 Ramp
Range ID232
This parameter defines the frequency range where the ramp time is related. Starting
from zero frequency.