Troubleshooting
Installer and user reference guide
145
R R8T7V1B
VRV IV heat pump for indoor installation
4P499898-1A – 2020.10
Main code
Sub code
Cause
Solution
Warning: faulty wiring to Q1/Q2
Check Q1/Q2 wiring. Do NOT use Q1/
Q2.
Malfunction code: faulty wiring to Q1/
Q2
Check Q1/Q2 wiring. Do NOT use Q1/
Q2.
▪
Too many indoor units are connected
to F1/F2 line
▪
Bad wiring between outdoor and
indoor units
Check indoor unit amount and total
capacity connected.
▪
System mismatch. Wrong type of
indoor units combined (R410A,
R407C,
RA,
etc).
Indoor
unit
malfunction
▪
Heat exchanger unit malfunction
▪
Check if other indoor units have
malfunction and confirm indoor unit
mix is allowed.
▪
Check the transmission wiring to the
heat exchanger unit.
More than 1 heat exchanger unit
connected.
Check installation. Only 1 heat
exchanger unit can be installed.
▪
Improper type of indoor units are
connected.
▪
Mismatch of compressor unit and
heat exchanger unit.
▪
Check the type of indoor units that
are currently connected. If they are
not proper, replace them with proper
ones.
▪
Check if the compressor unit and heat
exchanger unit are compatible.
5 HP heat exchanger unit connected.
Check installation. Connect 8 HP heat
exchanger unit.
▪
Auto
address
malfunction
(inconsistency)
▪
Mismatch of compressor unit and
heat exchanger unit.
▪
Check if transmission wired unit
amount matches with powered unit
amount (by monitor mode) or wait till
initialisation is finished.
▪
Check if the compressor unit and heat
exchanger unit are compatible.
▪
Auto
address
malfunction
(inconsistency)
▪
Mismatch of compressor unit and
heat exchanger unit.
▪
Check if transmission wired unit
amount matches with powered unit
amount (by monitor mode) or wait till
initialisation is finished.
▪
Check if the compressor unit and heat
exchanger unit are compatible.
▪
The stop valves of the compressor
unit are left closed.
▪
The piping and wiring of the specified
indoor unit or heat exchanger unit are
not connected correctly to the
compressor unit.
▪
Open the stop valves on both the gas
and liquid side.
▪
Confirm that the piping and wiring of
the specified indoor unit or heat
exchanger
unit
are
connected
correctly to the compressor unit.