23
|
Troubleshooting
Installer and user reference guide
142
R R8T7V1B
VRV IV heat pump for indoor installation
4P499898-1A – 2020.10
Main code
Cause
Solution
Malfunction code: System test run not yet
executed (system operation not possible)
Execute system test run.
▪
No power is supplied to the compressor unit.
▪
Transmission wiring malfunction
▪
Check if all units are powered on.
▪
Check the transmission wiring.
▪
System mismatch. Wrong type of indoor units
combined (R410A, R407C, RA, etc). Indoor
unit malfunction
▪
Heat exchanger unit malfunction
▪
Check if other indoor units have malfunction
and confirm indoor unit mix is allowed.
▪
Check the transmission wiring to the heat
exchanger unit.
▪
Improper type of indoor units are connected.
▪
Mismatch of compressor unit and heat
exchanger unit.
▪
Check the type of indoor units that are
currently connected. If they are not proper,
replace them with proper ones.
▪
Check if the compressor unit and heat
exchanger unit are compatible.
▪
The stop valves of the compressor unit are
left closed.
▪
The piping and wiring of the specified indoor
unit or heat exchanger unit are not connected
correctly to the compressor unit.
▪
Open the stop valves on both the gas and
liquid side.
▪
Confirm that the piping and wiring of the
specified indoor unit or heat exchanger unit
are connected correctly to the compressor
unit.
In case of 8 HP:
Main code
Sub code
Cause
Solution
▪
Heat exchanger fan malfunction.
▪
Drain pump feedback contact is open.
In the heat exchanger unit:
▪
Check connection on PCB: A1P (X15A)
▪
Check connection on terminal block
(X2M)
▪
Check the fan connectors.
Earth leakage detector activated
Compressor unit: (T1A) - A1P (X101A)
Restart the unit. If the problem
reoccurs, contact your dealer.
No earth leakage detector detected
Compressor unit: (T1A) - A1P (X101A)
Replace the earth leakage detector.
High pressure switch was activated
Compressor unit: (S1PH) - A1P (X4A)
Check stop valve situation or
abnormalities in (field) piping or airflow
over air cooled coil.
▪
Refrigerant overcharge
▪
Stop valve closed
▪
Check refrigerant recharge
unit.
▪
Open stop valves
Stop valve closed (liquid)
Open liquid stop valve.
▪
Refrigerant overcharge
▪
Stop valve closed
▪
Check refrigerant recharge
unit.
▪
Open stop valves.