23
|
Troubleshooting
Installer and user reference guide
143
R R8T7V1B
VRV IV heat pump for indoor installation
4P499898-1A – 2020.10
Main code
Sub code
Cause
Solution
Low pressure malfunction:
▪
Stop valve closed
▪
Refrigerant shortage
▪
Indoor unit malfunction
▪
Open stop valves.
▪
Check refrigerant recharge
unit.
▪
Check the user interface's display or
transmission wiring between the
outdoor unit and the indoor unit.
Electronic expansion valve malfunction
(subcool)
Compressor unit: (Y1E) - A1P (X21A)
Check connection on PCB or actuator.
Electronic expansion valve malfunction
(main)
Heat exchanger unit: (Y1E) - A1P (X7A)
Check connection on PCB or actuator.
Discharge temperature too high:
▪
Stop valve closed
▪
Refrigerant shortage
Compressor unit: (R21T) - A1P (X29A)
▪
Open stop valves.
▪
Check refrigerant recharge
unit.
▪
Refrigerant overcharge
▪
Stop valve closed
▪
Check refrigerant recharge
unit.
▪
Open stop valves.
Ambient temperature sensor
malfunction
Heat exchanger unit: (R1T) - A1P (X16A)
Check connection on PCB or actuator.
Discharge temperature sensor
malfunction
Compressor unit: (R21T): open circuit -
A1P (X29A)
Check connection on PCB or actuator.
Discharge temperature sensor
malfunction
Compressor unit: (R21T): short circuit -
A1P (X29A)
Check connection on PCB or actuator.
Heat exchanger gas sensor malfunction
Heat exchanger unit: (R2T) - A1P (X18A)
Check connection on PCB or actuator.
Suction temperature sensor
malfunction
Compressor unit: (R3T) - A1P (X30A)
Check connection on PCB or actuator.
Suction temperature sensor
malfunction
Compressor unit: (R7T) - A1P (X30A)
Check connection on PCB or actuator.
De-icing temperature sensor
malfunction
Heat exchanger unit: (R3T) - A1P (X17A)
Check connection on PCB or actuator
Содержание VRV IV RKXYQ5T8Y1B Series
Страница 155: ......
Страница 156: ...4P499898 1A 2020 10 Copyright 2017 Daikin Verantwortung f r Energie und Umwelt...