Electrical installation
Installer and user reference guide
106
R R8T7V1B
VRV IV heat pump for indoor installation
4P499898-1A – 2020.10
If
Then
≥1 MΩ
Insulation resistance is OK. This procedure is
finished.
<1 MΩ
Insulation resistance is not OK. Go to the next step.
2
Turn ON the power and leave it on for 6 hours.
Result:
The compressor will heat up and evaporate any refrigerant in the
compressor.
3
Measure the insulation resistance again.