19
|
Configuration
Installer and user reference guide
121
R R8T7V1B
VRV IV heat pump for indoor installation
4P499898-1A – 2020.10
Setting
Value
(8 HP)
(5 HP)
Description
[2‑30]
Power consumption limitation level
(step 1) via the external control adaptor
(DTA104A61/62).
If the system needs to be running under
power consumption limitation conditions
when an external signal is sent to the unit,
this setting defines the level power
consumption limitation that will be applied
for step 1. The level is according to the
table.
1
60%
2
—
65%
3
(default
)
(= binary 2) (default)
70%
4
—
75%
5
(= binary 4)
80%
6
—
85%
7
—
90%
8
—
95%
[2‑31]
Power consumption limitation level
(step 2) via the external control adaptor
(DTA104A61/62).
If the system needs to be running under
power consumption limitation conditions
when an external signal is sent to the unit,
this setting defines the level power
consumption limitation that will be applied
for step 2. The level is according to the
table.
—
(= binary 1)
30%
1
(default
)
(= binary 2) (default)
40%
2
(= binary 4)
50%
3
—
55%
[2‑32]
Forced, all time, power consumption
limitation operation (no external control
adaptor is required to perform power
consumption limitation).
If the system always needs to be running
under power consumption limitation
conditions, this setting activates and
defines the level power consumption
limitation that will be applied continuously.
The level is according to the table.
0
(default
)
(= binary 1) (default)
Function not active.
1
(= binary 2)
Follows [2‑30] setting.
2
(= binary 4)
Follows [2‑31] setting.
[2‑81] (in case of 8 HP)
(= binary [2‑41]) (in
case of 5 HP)
Cooling comfort setting.
This setting is used in conjunction with
setting [2‑8].
0
Eco
1
(default
)
(default)
Mild
2
Quick
3
Powerful