Startup and Shutdown Procedures
www.DaikinApplied.com 127
IOM 1207-6 • TRAILBLAZER
®
MODEL AGZ CHILLERS
Flow below
display range:
The SP LED will be lit red and the
left most LED will be flashing green. For example, if the SP
was set to 200 cm/s, the flashing labeled ‘0’ would indicate that
the flow was below 180 cm/s. This would be shown if no flow
through chiller or lowered than desired flow.
Figure 101: Display for Flow Below Range
Flow above
display range:
The SP LED will be lit amber, all
LEDs to the left and right of the SP LED with be green with the
right most LED flashing green. For example, if the SP was set
to 200 cm/s, the flashing LED labeled ‘9’ would indicate that
the flow was above 230 cm/s. This may be a normal display
depending on range by which flow varies through chiller.
Figure 102: Display for Flow Above Range