Circuit Functions
www.DaikinApplied.com 101
IOM 1207-6 • TRAILBLAZER
®
MODEL AGZ CHILLERS
Position Commands
In order to improve the reliability of the EXV positioning, the
position commands that are issued to the stepper driver are
limited in two ways:
1. Position commands are filtered so that the minimum change
in position is 0.3%. Changes of less than this are ignored. This
avoids unnecessary movement of the EXV and lowers the
chances of losing steps as a result.
2. The position commands are issued once per program cycle
with a maximum change of 0.7% each time. This allows the
stepper to move the valve to the commanded position before
the next position command is issued. Issuing commands in this
way may also lower the chances of losing steps.
EXV Position Range
The minimum EXV position while the circuit is running will
always be 8%. The maximum position will change as the
number of compressors running on the circuit changes. These
values are shown for each unit model in
Table 74: Maximum Position Range
Model
# Compressors Running/Circuit
1
2
3
AGZ030E
50
100
n/a
AGZ035E
50
100
n/a
AGZ040E
50
100
n/a
AGZ045E
50
100
n/a
AGZ050E
50
100
n/a
AGZ055E
50
100
n/a
AGZ060E
50
100
n/a
AGZ065E
50
100
n/a
AGZ070E
50
100
n/a
AGZ075E
60
100
n/a
AGZ080E
60
100
n/a
AGZ090E
60
100
n/a
AGZ100E
60
100
n/a
AGZ110E
50
80
n/a
AGZ120E
50
80
n/a
AGZ130E
50
80
n/a
AGZ140E
70
100
n/a
AGZ150E
70
100
n/a
AGZ161E
80
100
n/a
AGZ170E
60
80
100
AGZ180E
60
80
100
AGZ191E
60
80
100
AGZ211E
60
80
100
AGZ226E
60
80
100
AGZ241E
60
80
100
Operation Considerations
For all units - the expansion valve maximum position may
be increased if both the suction superheat is higher than the
target and the expansion valve has been within 1% of its
current maximum position for a minute. The maximum should
increase at a rate of 0.1% every six seconds up to a total of an
additional 10%. This addition to the maximum position should
be reset when the EXV is no longer in the Superheat Control
state, or a compressor on the circuit stages.
Manual Control
The EXV position can be set manually. Manual control can only
be selected when the circuit is in the run state. At any other
time, the EXV control set point is forced to auto.
When EXV control is set to manual, the EXV position is equal
to the manual EXV position setting. If set to manual when the
circuit state transitions from run to another state, the control
setting is automatically set back to auto. When in manual
control, the EXV control state displayed will be ‘Manual’.
Liquid Line Solenoid Valve
The liquid line solenoid output should be on when the circuit
state is either Pre-open or Run. This output should be off at all
other times.
Hot Gas Bypass Solenoid Valve
This output will be on when circuit state is Run for at least
30 seconds and one compressor on the unit is running. The
output should be off at all other times unless the unit is a model
191-241. For these models, the hot gas bypass will also be
activated for 10 minutes when a second or third compressor is
started on the circuit.
Capacity Overrides – Limits of
Operation
The following conditions shall override automatic capacity
control as described. These overrides keep the circuit from
entering a condition in which it is not designed to run.
Low Evaporator Pressure
If the Low Evaporator Pressure Hold or Low Evaporator
Pressure Unload alarms are triggered, the circuit capacity
may be limited or reduced. See the Circuit Events section for
details on triggering, reset, and actions taken.
High Condenser Pressure
If the High Condenser Pressure Unload alarm is triggered,
the circuit capacity may be limited or reduced. See the Circuit
Events section for details on triggering, reset, and actions
taken.