![Daikin Trailblazer AGZ030E-070E Скачать руководство пользователя страница 134](http://html.mh-extra.com/html/daikin/trailblazer-agz030e-070e/trailblazer-agz030e-070e_installation-operation-and-maintenance-manual_501731134.webp)
IOM 1207-6 • TRAILBLAZER
®
MODEL AGZ CHILLERS
134 www.DaikinApplied.com
Unit Maintenance
R-410A Refrigerant
Terminology
Bubble Point
: The temperature/pressure where bubbles first
appear when heat is added to a liquid refrigerant. Used to
measure sub-cooling.
Dew Point
: The temperature/pressure where droplets first
appear when heat is removed from a refrigerant gas. Used to
measure superheat.
Fractionalization
: A change in refrigerant composition due
to the tendency of the higher pressure refrigerant to leak at a
faster rate, should a system have leakage from a static two-
phase region.
Glide
: The total difference of Dew and Bubble Point at a
specific condition. Mid-Point or Mean: Measurement half way
between Dew and Bubble Points.
Miscibility
: The ability of a refrigerant and oil to mix and flow
together.
Solubility
: The effect of refrigerant on the viscosity of a
lubricant.
Safety
• ANSI/ASHRAE safety group A1.
• Always carry and be familiar with SDS information for
R-410a.
• Store refrigerant in clean, dry area out of direct sunlight.
• Never heat or store cylinders above 125° F. Note vehicle
precautions!
• Never tamper with cylinder valves or pressure relief
valves. (Typical relief for R-410A is 525 psig).
•
Never refill disposable cylinders.
• Verify cylinder hook-up.
• Verify cylinder label and color code match. R-410A is
rose/light maroon. Must be DOT approved, R-410A with
400 psig rating. Open cylinders slowly.
• Avoid rough handling of cylinders and secure as
appropriate. Cap when not in use.
•
Do not overfill recovery cylinders or overcharge units.
• Check gauge calibration before every use and manifold
set for leaks regularly.
• Be aware of pneumatic and possible hydrostatic pressure
potentials.
•
Never pressurize systems with oxygen or ref/air mix.
R-410A, R-407C, R-134A, & R-22 are flammable with low
air mix.
• Wear protective clothing. Impervious gloves and splash
goggles should be worn.
• Avoid contact with liquid refrigerant (R-410A -60.8°F @
atms.) due to corrosion and freezing hazards.
• Avoid exposure to vapors. 1000 ppm/8 hr.
• Evacuate areas in cases of large releases. R-410A is
heavier than air and can cause asphyxiation, narcotic and
cardiac sensation effects.
• Evacuate systems and break vacuum (0 psig) with
nitrogen before welding or brazing.
•
Always ventilate work areas before using open flames.
Exposure to open flames or glowing metal will form toxic
hydrofluoric acid & carbonyl fluoride. No smoking!
• Make sure all tools, equipment, and replacement
components are rated for the refrigerant used.
POE Lubricants
WARNING
POE oil must be handled carefully using proper protective
equipment (gloves, eye protection, etc.) The oil must not
come in contact with certain polymers (e.g. PVC), as it
may absorb moisture from this material. Daikin Applied
recommends against the use of PVC and CPVC piping
for chilled water systems. In the event the pipe is exposed
to POE oil used in the refrigerant system, the pipe can be
chemically damaged and pipe failure can occur. Also, do not
use oil or refrigerant additives in the system.
WARNING
Polyolester Oil, commonly known as POE oil is a synthetic
oil used in many refrigeration systems, and is present in this
Daikin product. POE oil, if ever in contact with PVC/CPVC, will
coat the inside wall of PVC/CPVC pipe causing environmental
stress fractures. Although there is no PVC/CPVC piping in
this product, please keep this in mind when selecting piping
materials for your application, as system failure and property
damage could result. Refer to the pipe manufacturer’s
recommendations to determine suitable applications of the
pipe.
POE type oil is used for compressor lubrication. This type of
oil is extremely hydroscopic which means it will quickly absorb
moisture if exposed to air and may form acids that can be
harmful to the chiller. Avoid prolonged exposure of POE oil to
the atmosphere to prevent this problem.
It is important that only the manufacturer’s recommended oils
be used. Acceptable POE oil types are:
•
CPI/Lubrizol Emkarate RL32-3 MAF
• Copeland Ultra 32-3 MAF
• Parker Emkarate RL32-3MAF
• Virginia LE323MAF
• Nu Calgon 4314-66
Procedure Notes
• Use only new sealed metal containers of oil to insure
quality.
• Buy smaller containers to prevent waste and
contamination.
•
Use only filter driers designed for POE and check
pressure drops frequently.
•
Test for acid and color at least annually. Change filter
driers if acid or high moisture (> 200 ppm) is indicated (<
Содержание Trailblazer AGZ030E-070E
Страница 4: ......
Страница 145: ... www DaikinApplied com 145 IOM 1207 6 TRAILBLAZER MODEL AGZ CHILLERS ...
Страница 146: ...IOM 1207 6 TRAILBLAZER MODEL AGZ CHILLERS 146 www DaikinApplied com ...