BAS Integration of Pumps
www.DaikinApplied.com 121
IOM 1207-6 • TRAILBLAZER
®
MODEL AGZ CHILLERS
Table 83: LONWORKS Network Parameters
Parameter
Value (Range)/Definition
Default Value
8-02 Control Source
Option A [3]/During initial pow er-up, the frequency converter automatically
sets this parameter to Option A [3] if it detects a valid fieldbus option
installed in slot A
FC Port [1]
11-0 Neuron ID
Variable/This is the neuron ID of the Lonw orks module.
Variable/This item w ill be blank if the
communication module is not commissioned.
11-10 Drive Profile
VSD Profile [0]/This parameter indicates the LONMARK functional profile VSD Profile [0]
11-15 LON
Warning Word
(0-FFFF)/This parameter contains LON specific w arnings.
Bit
Status
0
Internal Fault
1
Internal Fault
2
Internal Fault
3
Internal Fault
4
Internal Fault
5
Reserved
6
Reserved
N/A
7
Reserved
8
Reserved
9
Invalid type change for changeable types
10
Initialization error
11
Internal communication error
12
Software revision mismatch
13
Bus not active
14
Option not present
15
LON input (nvi/nci) exceeds limits
11-17 XIF Revision
0 N/A/This parameter contains the version of the external interface file on
the Neuron C chip on the LON option
0 N/A
11-18 LonWorks
Revision
0 N/A/This parameter contains the softw are version off the application
program on the Neuron C chip on the LON option.
0 N/A
11-21 Store Data
Values
Off [0] or Store all setups [2]/This parameter is used to activate storing of
data in non-volatile memory.
When activated (set to [2] Store all setups), all
parameters are stored in EEPROM; the value
returns to [2] Off w hen all parameter values
have been stored.
Table 84: MS Service LED - Red
Situation
LED Activity
Description
Configured state (normal operation)
½ sec. ON, then continuously OFF
The node is configures and running normally.
Non-configured state
Flashing ½ Hz
Node is not configures but has an application.
Proceed w ith loading node.
Applicationless state
1 sec. ON, 2 sec. OFF, then
continuously ON
Node has no application, the LonWorks option
needs replacing or reprogramming
Watchdog resets
Short flash about each 3 sec.
Indicates problem w ith application. The
LonWorks option needs replacing.
Faulty hardware
Steady ON or OFF
The LonWorks option needs replacing.