IOM 1207-6 • TRAILBLAZER
®
MODEL AGZ CHILLERS
28 www.DaikinApplied.com
Remote Evaporators
Figure 29: Remote Evaporator Piping Models 030-070
Figure 30: Remote Evaporator Piping Models 075-241
SUCTION
CIR. #2
SUCTION
CIR. #1
LIQUID
CIR. #1
LIQUID
CIR. #2
ENTERING WATER
TEMP SENSOR
LOCATION
STAINLESS STEEL
PIPE PLUG
BRAZE CONNECTIONS ON EVAP ARE STAINLESS STEEL,
SO FIELD MUST USE MIN 45% SILVER BRAZE ROD.
■-SIGHT GLASS (INCLUDED IN KIT)
■-FILTER DRIER, CORES, CLAMP & GASKET KITS (ALL INCLUDED IN KIT)
■-ELECTRIC EXPANSION VALVE AND CABLE (INCLUDED IN KIT)
LIQUID CIRCUIT #1
LIQUID CIRCUIT #2
WATER
OUTLET
WATER INLET
WATER STRAINER
REQUIRED
(SEPARATE KIT OR
FIELD SUPPLIED)
SCHRADER FITTINGS (FIELD SUPPLIED)
OPTIONAL HOT GAS BYPASS LINE MUST ENTER FROM VERTICAL POSITION AS SHOWN.
AGZ030-070E 4 FAN UNITS, WITH EXV
■ - DENOTES PARTS INCLUDED IN
REMOTE EVAP. SPECIALTIES KIT
CIRCUIT #1
COMPRESSORS
CIRCUIT #2
COMPRESSORS
LIQUID LINE
SHUTOFF VALVE
CIRCUIT #1
■-BALL VALVES WITH SCHRADER VALVES TO BE LOCATED
CLOSEST TO THE FILTER DRIER (INCLUDED IN KIT)
■-LIQUID LINE SOLENOID VALVE (INCLUDED IN KIT)
OPTION
HOT GAS BYPASS
CIRCUIT #1
OPTION
HOT GAS BYPASS
CIRCUIT #2
■-BALL VALVES WITH
SCHRADER VALVES TO BE
LOCATED CLOSEST TO THE
FILTER DRIER (INCLUDED IN KIT)
■-HOT GAS CHECK VALVES (INCLUDED IN KIT)
HGBP PIPING SLOPE TO EVAP.
1 INCH DOWN PER
10 FEET DISTANCE
4
■-ELECTRIC EXPANSION VALVE CABLES
(INCLUDED IN KIT)
RUN EXPANSION VALVE CABLE INTO BACK
OF CONTROL BOX AND CONNECT TO:
LIQUID LINE
SHUTOFF VALVE
CIRCUIT #2
STAINLESS STEEL SENSOR
WELL FOR LEAVING
WATER TEMP. SENSOR
LEAVING WATER
PIPE ASSEMBLY
VALVE
CORE
SUCTION
CIR. #2
SUCTION
CIR. #1
■-SUCTION PRESSURE
TRANSDUCERS, SCHRADER
FITTINGS WITH CORES
(INCLUDED IN KIT)
■-SUCTION TEMP. SENSOR TUBES
(INCLUDED IN KIT)
THE SUCTION TEMPERATURE SENSORS
AND TRANSDUCERS MUST BE LOCATED
AT THE EVAPORATOR AS SHOWN.
■-CHARGING VALVES
(INCLUDED IN KIT)
NOTES:
FOR FILTER DRIER SERVICE:
1.
ISOLATE DRIER BY CLOSING LIQUID LINE BALL
VALVES LOCATED ON BOTH SIDES OF DRIER.
LIQUID LINE SOLENOID & FILTER DRIER MUST BE
2.
LOCATED AT REMOTE EVAPORATOR.
SUPPORT FIELD PIPING AS REQUIRED.
3.
USED ONLY WHEN EVAPORATOR IS HIGHER
4.
THAN THE CONDENSING UNIT.
LIQUID LINE
SOLENOID VALVE HARNESSES
RUN SOLENOID VALVE HARNESSES INTO
BACK OF CONTROL BOX AND CONNECT TO:
CIR. #1: (E.E.X.V.1)
WHT TO M1+ ; BLK TO M1-
RED TO M2+ ; GRN TO M2-
CIR. #2: (E.E.X.V.2)
WHT TO M1+ ; BLK TO M1-
RED TO M2+ ; GRN TO M2-
CIR. #1: RED #1 TO TB2-91
WHT #2 TO TB1-29
CIR. #2: RED #1 TO TB2-92
WHT #2 TO TB1-29
WIRING AND CONDUIT ARE FIELD
SUPPLIED.
■-MOV SOLENOID CONNECTORS
ARE INCLUDED IN KIT.
334705191