![Daikin Trailblazer AGZ030E-070E Скачать руководство пользователя страница 108](http://html.mh-extra.com/html/daikin/trailblazer-agz030e-070e/trailblazer-agz030e-070e_installation-operation-and-maintenance-manual_501731108.webp)
IOM 1207-6 • TRAILBLAZER
®
MODEL AGZ CHILLERS
108 www.DaikinApplied.com
Using the Controller
Passwords
There are 4 levels of access for the user interface:
• No password
• Operator level - 5321
• Technician/Manager level - 2526
• Daikin Applied service technician level
Enter passwords from the Main Menu:
• Enter Password links to the Entry screen which is an
editable screen. So pressing the wheel goes to the edit
mode where the password can be entered. The first (*)
will be highlighted, rotate the wheel clockwise to the first
number and set it by pressing the wheel. Repeat for the
remaining three numbers. The password will time out
after 10 minutes and is cancelled if a new password is
entered or the control powers down.
• Not entering a password allows access to a limited
number of parameters as shown in
Figure 81: Password Menu
Main Menu
1/3
Enter Password >
Unit Status
Off: Unit Sw
ACTIVE SETPT 44.6°F
Figure 82: Password Entry Page
Enter Password
1/1
Enter PW ****
Entering an invalid password has the same effect as not
entering a password.
Once a valid password has been entered, the controller
allows further changes and access without requiring the user
to enter a password until either the password timer expires
or a different password is entered. The default value for this
password timer is 10 minutes.
Navigation Mode
When the navigation wheel is turned clockwise, the cursor
moves to the next line (down) on the page. When the wheel is
turned counter-clockwise the cursor moves to the previous line
(up) on the page. The faster the wheel is turned the faster the
cursor moves. Pushing the wheel acts as an “Enter” button.
Three types of lines exist:
•
Menu title, displayed in the first line as in
.
• Link (also called Jump) having an arrow ( > ) in the right
of the line and used to link to the next menu.
• Parameters with a value or adjustable setpoint.
For example, “Time Until Restart” jumps from level 1 to level 2
and stops there.
When the Back Button is pressed the display reverts back to
the previously displayed page. If the Back button is repeatedly
pressed the display continues to revert one page back along
the current navigation path until the “main menu” is reached.
When the Menu (Home) Button is pressed the display reverts
to the “main page.”
When the Alarm Button is depressed, the Alarm Lists menu is
displayed.
Edit Mode
The Editing Mode is entered by pressing the navigation wheel
while the cursor is pointing to a line containing an editable field.
Once in the edit mode pressing the wheel again causes the
editable field to be highlighted. Turning the wheel clockwise
while the editable field is highlighted causes the value to be
increased. Turning the wheel counter-clockwise while the
editable field is highlighted causes the value to be decreased.
The faster the wheel is turned the faster the value is increased
or decreased. Pressing the wheel again cause the new value
to be saved and the keypad/display to leave the edit mode and
return to the navigation mode.
A parameter with an “R” is read only; it is giving a value or
description of a condition. An “R/W“ indicates a read and/or
write opportunity; a value can be read or changed (providing
the proper password has been entered).
Link and parameter access is indicated for the various
password levels with one column for each level. Column
headings for the password levels are as follows and shown in
N = No password
O = Operator level
T = Technician/Manager level
D = Daikin Applied factory service technician level
Screen navigational links:
• For each link on a screen, the linked screen is indicated
in the rightmost column.
• For each screen, the screen(s) from which you can
navigate to it is also shown in parentheses after the
screen identifier.
• For most circuit or compressor level parameters, there
is a link to a screen that shows the values for all circuits/
compressors which is indicated in the ‘Links to screen’
column as *.
For many of the circuit level screens, only one screen will be
shown in this section. The same set of screens exists for each
circuit and compressor. These screens are the ones with ‘Cx’
and Cmpx’ identifiers.
Figure 83: Example of Screen Menu With Access Levels