SiE25-110
Function Details
Function and Operation
83
4.2.4 Simulated operation Function
Outside temperature thermistor
Outdoor unit heat exchange thermistor
Fin thermistor
Discharge pipe thermistor
Indoor unit suction thermistor
Indoor unit heat exchanger thermistor
When malfunctions, quasi-operation is conducted while displaying the applicable alarm. (If the
fin thermistor malfunctions, the alarm is not displayed on the remote controller, and displayed
only when pushing Inspection Button.)
If low pressure sensor or suction pipe thermistor malfunctions, compressor stops operation due
to malfunction and does not conduct the simulated-operation.
4.2.5 Capacitor Discharging Control
Outputs non-phase waveform for condenser to discharge for about 1 minute after K11R turns
OFF (remote controller stop, stop due to malfunction, compressor and outdoor unit fan motor
stop with thermostat OFF in the retry system).
4.2.6 Thermostat ON/OFF judgement
Room temperature thermostat control
Thermostat ON
∆
Trs
≥
0˚C
Thermostat OFF Executes thermostat OFF when either one of the following conditions is met.
∆
Trs
≤
–1.0˚C continues for 1 minutes.
Cooling:
∆
Trs
≤
–2.5˚C
Heating:
∆
Trs
≤
–3.0˚C
∆
Trs
≥
1.0˚C changed suddenly into
∆
Trs
≥
–1.5˚C.
∆
Trs = [Indoor suction temperature] - [Remote controller set temperature] –0.5˚C
4.2.7 “Automatic Operation Mode” Control (PMV Control)
When selecting “Automatic Operation Mode” with the remote controller, conducts the most
comfortable operation in which you do not feel too cool or too hot.
Outdoor air temperature
Indoor air temperature
Remote controller set temperature
Calculates and controls the
optimum indoor temperature
(S2565)
Содержание SkyAir Super Inverter 70 D Series
Страница 11: ...SiE25 110 2...
Страница 15: ...Model Name and Power Supply SiE25 110 6 Model Name and Power Supply...
Страница 16: ...SiE25 110 Functions 7 Part 2 Functions 1 List of Functions 8 1 1 Functions 8...
Страница 31: ...Specifications SiE25 110 22 Specifications...
Страница 35: ...Wired Remote Controller SiE25 110 26 Remote Controller 1 2 Installation...
Страница 36: ...SiE25 110 Wired Remote Controller Remote Controller 27...
Страница 39: ...Wireless Remote Controller SiE25 110 30 Remote Controller...
Страница 63: ...Settings Concerning Maintenance SiE25 110 54 Field Setting FUYP...
Страница 64: ...SiE25 110 Settings Concerning Maintenance Field Setting 55 FHYP...
Страница 65: ...Settings Concerning Maintenance SiE25 110 56 Field Setting FAYP...
Страница 67: ...Settings Concerning Maintenance SiE25 110 58 Field Setting RZP100 125DV1 E RZP100DVAL E...
Страница 68: ...SiE25 110 Settings Concerning Maintenance Field Setting 59 RZP125 140DTAL...
Страница 107: ...Operation Range SiE25 110 98 Function and Operation 5 Operation Range 5 1 Operation Limits...
Страница 133: ...Procedure of Self Diagnosis by Remote Controller SiE25 110 124 Troubleshooting...
Страница 238: ...SiE25 110 Piping Diagrams Appendix 229 1 2 Twin System RZP100D RZP125D 3D034162...
Страница 240: ...SiE25 110 Wiring Diagrams Appendix 231 FHYP45BV1 FHYP60BV1 FHYP71BV1 FHYP100BV1 FHYP125BV1 3D027503...
Страница 241: ...Wiring Diagrams SiE25 110 232 Appendix FUYP71BV1 FUYP100BV1 FUYP125BV1 3D027747...
Страница 242: ...SiE25 110 Wiring Diagrams Appendix 233 FAYP71BV1 FAYP100BV1 3D027748...
Страница 243: ...Wiring Diagrams SiE25 110 234 Appendix 2 2 Outdoor Units 2 2 1 50Hz RZP71DV1 3D032604...
Страница 244: ...SiE25 110 Wiring Diagrams Appendix 235 RZP100DV1 RZP125DV1 3D032603...
Страница 245: ...Wiring Diagrams SiE25 110 236 Appendix 2 2 2 60Hz RZP71DVAL 3D032880B...
Страница 246: ...SiE25 110 Wiring Diagrams Appendix 237 RZP100DVAL 3D032881B...
Страница 247: ...Wiring Diagrams SiE25 110 238 Appendix RZP125DTAL RZP140DTAL 3D032882B...
Страница 251: ...SiE25 110 iv Index...