Field Piping and Wiring
SiE25-110
38
Field Piping and Wiring
WARNING
Electrical wiring must be carried out by qualified personnel.
Before obtainging access to terminal devices, all supply circuits munt be interrupted.
CAUTION
Be sure to ground the air conditioner.
Do not connect the earth wire to a gas pipe, water pipe, lightning conductor or telephone earth wire.
Use only copper wires.
The wiring between the indoor unit and outdoor unit must be for 220V.
Do not turn on the main switch until all the wiring is complated.
The resistance of the grounding must not exceed 500 .
When performing electrical wiring, refer also to the wiring diagram affixed to the unit.
Use the specified wires and fix them with clamps so that no external forces act on the terminals. For clamp-
ing, push the hook in tail end of the clamp to loosen it, pass the wires through it, then fasten the clamp.
Clamp the wiring as shown below, taking care that the wires do not touch the piping. (especially high-pres-
sure piping)
Never squeeze extra wires into the unit.
When leading out the wires to the front or side, you can use a wire conduit passing through the knock-out
hole ( 34mm). When you don’t use a wire conduit, be sure to protect the wires with vinyl tubes etc. to pre-
vent the edge of the knock-out hole from cutting the wires.
Form the wires and fix the cover firmly so that the cover may be fit in properly.
CAUTIONS
As this unit is equipped with an inverter, installing a phase advancing capacitor not only will deteriorate
power factor improvement effect, but also may cause a capacitor abnomal heating accident due to high-fre-
quency waves. Therefore never install a phase advancing capacitor.
keep power imbalance to within 2% of the supply rating.
1. Large imbalance will shorten the life of the smoothing capacitor.
2. As a protective measure, the product will stop operating and an error indication will be made, when
power imbalance exceeds 4% of the supply rating.
When installing the leakage breaker make sure it is an inverter-type (high-frequency/high-freq. non-sensing
type) breaker.
Switch box
Ground
Switch
box
Ground
Clamp (attached)
Clamp
Clamp
(attached)
Clamp
Wiring
between
units
Stop valve
mounting plate
Clamp
Hook
Power supply and
ground wiring
Power supply and
ground wiring
Wiring between
units
Stop valve
mounting plate
1 2 3 L
N
VAL Model
1 2 3 R S T
TAL Model
When using 71 model
When using 100 · 125 · 140 model
Wiring between units
Wiring between
units
Back
Power supply
and ground
wiring
To the side
Down
Forward
Insulation tubing
Insulation tubing
The service ports and the four-way switch
valve have been covered by insulation
tubing in order to protect wiring from high
temperatures. Do not remove this tubing
for any reason other than for service work.
If it is removed, be sure to replace it and
secure it with the clamping material.
Note:
Содержание SkyAir Super Inverter 70 D Series
Страница 11: ...SiE25 110 2...
Страница 15: ...Model Name and Power Supply SiE25 110 6 Model Name and Power Supply...
Страница 16: ...SiE25 110 Functions 7 Part 2 Functions 1 List of Functions 8 1 1 Functions 8...
Страница 31: ...Specifications SiE25 110 22 Specifications...
Страница 35: ...Wired Remote Controller SiE25 110 26 Remote Controller 1 2 Installation...
Страница 36: ...SiE25 110 Wired Remote Controller Remote Controller 27...
Страница 39: ...Wireless Remote Controller SiE25 110 30 Remote Controller...
Страница 63: ...Settings Concerning Maintenance SiE25 110 54 Field Setting FUYP...
Страница 64: ...SiE25 110 Settings Concerning Maintenance Field Setting 55 FHYP...
Страница 65: ...Settings Concerning Maintenance SiE25 110 56 Field Setting FAYP...
Страница 67: ...Settings Concerning Maintenance SiE25 110 58 Field Setting RZP100 125DV1 E RZP100DVAL E...
Страница 68: ...SiE25 110 Settings Concerning Maintenance Field Setting 59 RZP125 140DTAL...
Страница 107: ...Operation Range SiE25 110 98 Function and Operation 5 Operation Range 5 1 Operation Limits...
Страница 133: ...Procedure of Self Diagnosis by Remote Controller SiE25 110 124 Troubleshooting...
Страница 238: ...SiE25 110 Piping Diagrams Appendix 229 1 2 Twin System RZP100D RZP125D 3D034162...
Страница 240: ...SiE25 110 Wiring Diagrams Appendix 231 FHYP45BV1 FHYP60BV1 FHYP71BV1 FHYP100BV1 FHYP125BV1 3D027503...
Страница 241: ...Wiring Diagrams SiE25 110 232 Appendix FUYP71BV1 FUYP100BV1 FUYP125BV1 3D027747...
Страница 242: ...SiE25 110 Wiring Diagrams Appendix 233 FAYP71BV1 FAYP100BV1 3D027748...
Страница 243: ...Wiring Diagrams SiE25 110 234 Appendix 2 2 Outdoor Units 2 2 1 50Hz RZP71DV1 3D032604...
Страница 244: ...SiE25 110 Wiring Diagrams Appendix 235 RZP100DV1 RZP125DV1 3D032603...
Страница 245: ...Wiring Diagrams SiE25 110 236 Appendix 2 2 2 60Hz RZP71DVAL 3D032880B...
Страница 246: ...SiE25 110 Wiring Diagrams Appendix 237 RZP100DVAL 3D032881B...
Страница 247: ...Wiring Diagrams SiE25 110 238 Appendix RZP125DTAL RZP140DTAL 3D032882B...
Страница 251: ...SiE25 110 iv Index...