SiE25-110
Maintenance Inspections
Troubleshooting
101
1. Maintenance Inspections
1.1
Optimal Operation Condition
Guide Lines for
Optimal
Operation
Condition
The operation value guide lines when operating under standard conditions (at Rated
frequency) by pushing the test run button on the remote controller are as given in the table
below. RZ(Y)71~125L are used as example outdoor units in the table.
Indoor Unit Fan: “H” Operation Compressor: Rated Frequency
Note:
Figures given inside parentheses are in unit of kg/cm
²
Standard Conditions
During or after maintenance, when the power supply is turned back on, operation restarts
automatically by the “auto restart function.” Please exercise the proper caution.
High
Pressure
(Mpa)
Low
Pressure
(Mpa)
Discharge
Pipe
Temperature
(˚C)
Suction
Temperature
(˚C)
Indoor Unit
Side:
Differential
Between
Suction
Temperature
and
Discharge
Temperature
(˚C)
Outdoor Unit
Side:
Differential
Between
Suction
Temperature
and
Discharge
Temperature
(˚C)
Cooling 50Hz
1.62~2.11
(16.5~21.5)
0.39~0.59
(4.0~6.0)
60~95
0~14
8~18
7~12
60Hz
1.72~2.21
(17.5~22.5)
0.34~0.54
(3.5~5.5)
70~115
–2~10
Heating 50Hz
1.42~2.06
(14.5~21.0)
0.29~0.44
(3.0~4.5)
55~95
–4~4
14~30
2~6
60Hz
1.62~2.11
(16.5~21.5)
0.29~0.44
(3.0~4.5)
60~115
–6~2
Indoor Unit Conditions
Outdoor Unit Conditions
Cooling Operation
27˚C DB/19˚C WB
35˚C DB
Heating Operation
20˚C DB
7˚C DB/6˚C WB
Содержание SkyAir Super Inverter 70 D Series
Страница 11: ...SiE25 110 2...
Страница 15: ...Model Name and Power Supply SiE25 110 6 Model Name and Power Supply...
Страница 16: ...SiE25 110 Functions 7 Part 2 Functions 1 List of Functions 8 1 1 Functions 8...
Страница 31: ...Specifications SiE25 110 22 Specifications...
Страница 35: ...Wired Remote Controller SiE25 110 26 Remote Controller 1 2 Installation...
Страница 36: ...SiE25 110 Wired Remote Controller Remote Controller 27...
Страница 39: ...Wireless Remote Controller SiE25 110 30 Remote Controller...
Страница 63: ...Settings Concerning Maintenance SiE25 110 54 Field Setting FUYP...
Страница 64: ...SiE25 110 Settings Concerning Maintenance Field Setting 55 FHYP...
Страница 65: ...Settings Concerning Maintenance SiE25 110 56 Field Setting FAYP...
Страница 67: ...Settings Concerning Maintenance SiE25 110 58 Field Setting RZP100 125DV1 E RZP100DVAL E...
Страница 68: ...SiE25 110 Settings Concerning Maintenance Field Setting 59 RZP125 140DTAL...
Страница 107: ...Operation Range SiE25 110 98 Function and Operation 5 Operation Range 5 1 Operation Limits...
Страница 133: ...Procedure of Self Diagnosis by Remote Controller SiE25 110 124 Troubleshooting...
Страница 238: ...SiE25 110 Piping Diagrams Appendix 229 1 2 Twin System RZP100D RZP125D 3D034162...
Страница 240: ...SiE25 110 Wiring Diagrams Appendix 231 FHYP45BV1 FHYP60BV1 FHYP71BV1 FHYP100BV1 FHYP125BV1 3D027503...
Страница 241: ...Wiring Diagrams SiE25 110 232 Appendix FUYP71BV1 FUYP100BV1 FUYP125BV1 3D027747...
Страница 242: ...SiE25 110 Wiring Diagrams Appendix 233 FAYP71BV1 FAYP100BV1 3D027748...
Страница 243: ...Wiring Diagrams SiE25 110 234 Appendix 2 2 Outdoor Units 2 2 1 50Hz RZP71DV1 3D032604...
Страница 244: ...SiE25 110 Wiring Diagrams Appendix 235 RZP100DV1 RZP125DV1 3D032603...
Страница 245: ...Wiring Diagrams SiE25 110 236 Appendix 2 2 2 60Hz RZP71DVAL 3D032880B...
Страница 246: ...SiE25 110 Wiring Diagrams Appendix 237 RZP100DVAL 3D032881B...
Страница 247: ...Wiring Diagrams SiE25 110 238 Appendix RZP125DTAL RZP140DTAL 3D032882B...
Страница 251: ...SiE25 110 iv Index...