Troubleshooting by Remote Controller Display / LED Display
SiE25-110
176
Troubleshooting
6.33 Malfunction of Radiator Fin Temperature Thermistor
Remote
Controller
Display
P4
Outdoor Unit LED
Display
A
5
1
4
2
4
3
3
4
3
Applicable
Models
RZP71~140D
Method of
Malfunction
Detection
Detection by open or short circuit of the radiator fin temperature thermistor during the
compressor stops operating.
Malfunction
Decision
Conditions
When open or short circuit of the radiator fin temperature thermistor is detected during the
compressor stops operating
Supposed
Causes
Faulty inverter PC board
Faulty radiator fin temperature thermistor
(Independent replacement of the thermistor is not allowed.)
Troubleshooting
Check LED on the outdoor
unit PC board.
Reset
YES
Probe other factors than malfunction.
Does
the radiator
fin temperature
thermistor
malfunction?
NO
Replace the inverter PC board.
Is reset possible?
NO
YES
*
1. This error code is displayed only when button is pushed. While the normal operation still
continues, inverter protection cannot be actuated.
*
2. On this unit, the radiator fin temperature thermistor cannot be mantled/dismantled
independently. Replace by inverter PC board.
*
3. See
Check 12
for “Thermistor temperature/Resistance characteristics”.
TEST
(S2600)
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
Содержание SkyAir Super Inverter 70 D Series
Страница 11: ...SiE25 110 2...
Страница 15: ...Model Name and Power Supply SiE25 110 6 Model Name and Power Supply...
Страница 16: ...SiE25 110 Functions 7 Part 2 Functions 1 List of Functions 8 1 1 Functions 8...
Страница 31: ...Specifications SiE25 110 22 Specifications...
Страница 35: ...Wired Remote Controller SiE25 110 26 Remote Controller 1 2 Installation...
Страница 36: ...SiE25 110 Wired Remote Controller Remote Controller 27...
Страница 39: ...Wireless Remote Controller SiE25 110 30 Remote Controller...
Страница 63: ...Settings Concerning Maintenance SiE25 110 54 Field Setting FUYP...
Страница 64: ...SiE25 110 Settings Concerning Maintenance Field Setting 55 FHYP...
Страница 65: ...Settings Concerning Maintenance SiE25 110 56 Field Setting FAYP...
Страница 67: ...Settings Concerning Maintenance SiE25 110 58 Field Setting RZP100 125DV1 E RZP100DVAL E...
Страница 68: ...SiE25 110 Settings Concerning Maintenance Field Setting 59 RZP125 140DTAL...
Страница 107: ...Operation Range SiE25 110 98 Function and Operation 5 Operation Range 5 1 Operation Limits...
Страница 133: ...Procedure of Self Diagnosis by Remote Controller SiE25 110 124 Troubleshooting...
Страница 238: ...SiE25 110 Piping Diagrams Appendix 229 1 2 Twin System RZP100D RZP125D 3D034162...
Страница 240: ...SiE25 110 Wiring Diagrams Appendix 231 FHYP45BV1 FHYP60BV1 FHYP71BV1 FHYP100BV1 FHYP125BV1 3D027503...
Страница 241: ...Wiring Diagrams SiE25 110 232 Appendix FUYP71BV1 FUYP100BV1 FUYP125BV1 3D027747...
Страница 242: ...SiE25 110 Wiring Diagrams Appendix 233 FAYP71BV1 FAYP100BV1 3D027748...
Страница 243: ...Wiring Diagrams SiE25 110 234 Appendix 2 2 Outdoor Units 2 2 1 50Hz RZP71DV1 3D032604...
Страница 244: ...SiE25 110 Wiring Diagrams Appendix 235 RZP100DV1 RZP125DV1 3D032603...
Страница 245: ...Wiring Diagrams SiE25 110 236 Appendix 2 2 2 60Hz RZP71DVAL 3D032880B...
Страница 246: ...SiE25 110 Wiring Diagrams Appendix 237 RZP100DVAL 3D032881B...
Страница 247: ...Wiring Diagrams SiE25 110 238 Appendix RZP125DTAL RZP140DTAL 3D032882B...
Страница 251: ...SiE25 110 iv Index...