SiE25-110
Troubleshooting by Remote Controller Display / LED Display
Troubleshooting
161
6.23 Malfunction of outdoor fan motor signal
Remote
Controller
Display
H7
Outdoor Unit LED
Display
Applicable
Models
RZP71 ~ 140D
Method of
Malfunction
Detection
Detection of signal malfunction from outdoor fan motor
Malfunction
Decision
Conditions
When malfunction signal is detected at the start of fan motor operation.
Supposed
Causes
Malfunction of fan motor signal (circuit failure)
Disconnection, short of fan motor lead wire and coming off the connector
Faulty PC board
Troubleshooting
Is the connector(
*
)
of fan motor
connected correctly?
NO
YES
YES
Is the resistance value
normal in above
connector check?
NO
Connect correctly.
Replace the fan motor.
Replace the PC board.
(S2588)
Check No. 9
Check the fan motor
connector
*
Connector symbol of fan motor
0
Caution for service
If the outdoor fan rotates due to strong wind, voltage generates in main circuit capacitor.
To prevent electric shock, make sure the low voltage of main circuit (50 VDC or lower)
before carrying out troubleshooting. To prevent PC board from being damaged, touch
the earth connector in an electric parts box immediately before the inserting and
extracting the connector, which discharges the static from human body.
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
Disconnect the power supply
Model name
RZP71D
RZP100 to 140D
Connector symbol
X206A
X206A, X207A
Содержание SkyAir Super Inverter 70 D Series
Страница 11: ...SiE25 110 2...
Страница 15: ...Model Name and Power Supply SiE25 110 6 Model Name and Power Supply...
Страница 16: ...SiE25 110 Functions 7 Part 2 Functions 1 List of Functions 8 1 1 Functions 8...
Страница 31: ...Specifications SiE25 110 22 Specifications...
Страница 35: ...Wired Remote Controller SiE25 110 26 Remote Controller 1 2 Installation...
Страница 36: ...SiE25 110 Wired Remote Controller Remote Controller 27...
Страница 39: ...Wireless Remote Controller SiE25 110 30 Remote Controller...
Страница 63: ...Settings Concerning Maintenance SiE25 110 54 Field Setting FUYP...
Страница 64: ...SiE25 110 Settings Concerning Maintenance Field Setting 55 FHYP...
Страница 65: ...Settings Concerning Maintenance SiE25 110 56 Field Setting FAYP...
Страница 67: ...Settings Concerning Maintenance SiE25 110 58 Field Setting RZP100 125DV1 E RZP100DVAL E...
Страница 68: ...SiE25 110 Settings Concerning Maintenance Field Setting 59 RZP125 140DTAL...
Страница 107: ...Operation Range SiE25 110 98 Function and Operation 5 Operation Range 5 1 Operation Limits...
Страница 133: ...Procedure of Self Diagnosis by Remote Controller SiE25 110 124 Troubleshooting...
Страница 238: ...SiE25 110 Piping Diagrams Appendix 229 1 2 Twin System RZP100D RZP125D 3D034162...
Страница 240: ...SiE25 110 Wiring Diagrams Appendix 231 FHYP45BV1 FHYP60BV1 FHYP71BV1 FHYP100BV1 FHYP125BV1 3D027503...
Страница 241: ...Wiring Diagrams SiE25 110 232 Appendix FUYP71BV1 FUYP100BV1 FUYP125BV1 3D027747...
Страница 242: ...SiE25 110 Wiring Diagrams Appendix 233 FAYP71BV1 FAYP100BV1 3D027748...
Страница 243: ...Wiring Diagrams SiE25 110 234 Appendix 2 2 Outdoor Units 2 2 1 50Hz RZP71DV1 3D032604...
Страница 244: ...SiE25 110 Wiring Diagrams Appendix 235 RZP100DV1 RZP125DV1 3D032603...
Страница 245: ...Wiring Diagrams SiE25 110 236 Appendix 2 2 2 60Hz RZP71DVAL 3D032880B...
Страница 246: ...SiE25 110 Wiring Diagrams Appendix 237 RZP100DVAL 3D032881B...
Страница 247: ...Wiring Diagrams SiE25 110 238 Appendix RZP125DTAL RZP140DTAL 3D032882B...
Страница 251: ...SiE25 110 iv Index...