Function Details
SiE25-110
94
Function and Operation
[Defrost control]
[Defrost ending condition]
Defrosting ends when the following conditions have been realized after 1 minute elapsed from
defrosting start. Note that defrosting can be operated for 10 minutes at longest.
4.2.25 Pump down residual operation
Conducts pump down residual operation when compressor stops to collect refrigerant in
evaporator for preventing liquid refrigerant from remaining in the evaporator.
[Contents of control]
Compressor:For RZP71D; 41 Hz
For RZP100~140D; 110 Hz
Motorized valve: 0 pls (fixed opening degree)
Solenoid valve for receiver gas purging (SVG): ON (open)
[Ending condition]
Model RZP71D
Model RZP100~140D
AHz
172Hz
210Hz
BHz
134Hz
177Hz
CHz
48Hz
74Hz
D pls
95 pls
95 pls (RZP100D)
135 pls (RZP125D)
154 pls (RZP140D)
A Hz
ON
OFF
ON
ON
OFF
ON
ON
ON
OFF
ON
B Hz
C Hz
D pls
480 pls
D pls
Previous control
Compressor
4-way valve
Motorized valve
Outdoor unit fan
Indoor fan
Solenoid valve (SVG)
Defrosting complete
Defrosting start
(S2557)
Outdoor unit heat exchanger outlet temperature (Tb)
≥
10˚C
High pressure (Hp)
≥
2.16 MPa
OR
(S2558)
30 seconds elapsed with residual operation
LP<0.1 MPa (when cooling)
LP<0.02 MPa (when heating)
OR
(S2561)
Содержание SkyAir Super Inverter 70 D Series
Страница 11: ...SiE25 110 2...
Страница 15: ...Model Name and Power Supply SiE25 110 6 Model Name and Power Supply...
Страница 16: ...SiE25 110 Functions 7 Part 2 Functions 1 List of Functions 8 1 1 Functions 8...
Страница 31: ...Specifications SiE25 110 22 Specifications...
Страница 35: ...Wired Remote Controller SiE25 110 26 Remote Controller 1 2 Installation...
Страница 36: ...SiE25 110 Wired Remote Controller Remote Controller 27...
Страница 39: ...Wireless Remote Controller SiE25 110 30 Remote Controller...
Страница 63: ...Settings Concerning Maintenance SiE25 110 54 Field Setting FUYP...
Страница 64: ...SiE25 110 Settings Concerning Maintenance Field Setting 55 FHYP...
Страница 65: ...Settings Concerning Maintenance SiE25 110 56 Field Setting FAYP...
Страница 67: ...Settings Concerning Maintenance SiE25 110 58 Field Setting RZP100 125DV1 E RZP100DVAL E...
Страница 68: ...SiE25 110 Settings Concerning Maintenance Field Setting 59 RZP125 140DTAL...
Страница 107: ...Operation Range SiE25 110 98 Function and Operation 5 Operation Range 5 1 Operation Limits...
Страница 133: ...Procedure of Self Diagnosis by Remote Controller SiE25 110 124 Troubleshooting...
Страница 238: ...SiE25 110 Piping Diagrams Appendix 229 1 2 Twin System RZP100D RZP125D 3D034162...
Страница 240: ...SiE25 110 Wiring Diagrams Appendix 231 FHYP45BV1 FHYP60BV1 FHYP71BV1 FHYP100BV1 FHYP125BV1 3D027503...
Страница 241: ...Wiring Diagrams SiE25 110 232 Appendix FUYP71BV1 FUYP100BV1 FUYP125BV1 3D027747...
Страница 242: ...SiE25 110 Wiring Diagrams Appendix 233 FAYP71BV1 FAYP100BV1 3D027748...
Страница 243: ...Wiring Diagrams SiE25 110 234 Appendix 2 2 Outdoor Units 2 2 1 50Hz RZP71DV1 3D032604...
Страница 244: ...SiE25 110 Wiring Diagrams Appendix 235 RZP100DV1 RZP125DV1 3D032603...
Страница 245: ...Wiring Diagrams SiE25 110 236 Appendix 2 2 2 60Hz RZP71DVAL 3D032880B...
Страница 246: ...SiE25 110 Wiring Diagrams Appendix 237 RZP100DVAL 3D032881B...
Страница 247: ...Wiring Diagrams SiE25 110 238 Appendix RZP125DTAL RZP140DTAL 3D032882B...
Страница 251: ...SiE25 110 iv Index...