FXDQ-SPV1 EDTFVN391825

26

3P347455-11H

13. Installation Manual

1

Inverter Air Conditioner

Installation Manual

CONTENTS

1

2

3

3

4

5

6

8

8

10

13

1. SAFETY PRECAUTIONS

The air conditioner is a Level A product. When it is used 

in house, there is possibility of causing radio interference, 

and in case of such phenomena, the user shall take the 

corresponding countermeasures.

Before installing the air conditioner, please carefully read 

the “SAFETY PRECAUTIONS” to ensure correct installation.

This air conditioner comes under the term “applianes 

not accessible to general public”

. The precautions 

indicated below are divided into two types. The two types 

of precautions are related to safety and very important, 

so please carefully read the precautions.

WARNING......Situations as death or severe injury 

                        can occur in case of noncompliance.

CAUTION.......Situations as injury or damage to the 

                        machine can occur in case of 

                        noncompliance.

                        Depending on different situations, 

                        situations as severe injury can occur.

After installation, please carry out test run to confirm 

whether the machine operates normally. And please give 

instructions on the use and maintenance of the air conditioner 

to the user. Ask the user to keep the installation manual 

and the operation manual well for future references.

WARNING

· 

The installation work shall be carried out by the dealer 

   or professional personnel. Do not operate by yourself 

   without authorization.

   Incorrect installation may lead to water leakage, electrical 

   shock and fire.

· 

Please follow the steps in the instruction manual to install.

   Incorrect installation may lead to water leakage, electrical 

   shock and fire.

· 

When it is installed in a small room, the corresponding 

   measures shall be taken to prevent the concentration of 

   the refrigerant in the room from exceeding the limit in case 

   of any leakage of the refrigerant. Please consult the dealer 

   for the corresponding countermeasures.

   When the concentration of the refrigerant in a confined 

   space is too high, insufficient oxygen can occur.

· 

Always use the specified parts to install.

   In case that the installation is not carried out with the 

   specified parts, such issues as air conditioner falling, water 

   leakage, electrical shock, fire or incorrect operation can occur.

· 

Please install the air conditioner in a firm place which is 

   sufficient to withstand its weight.

   In case that the base is not firm, the air conditioner may 

   fall down and damages can occur.

· 

Take full considerations on influences from strong wind, 

   typhoon and earthquake, and reinforce the installation.

   Incorrect installation can lead to falling off of the air 

   conditioner and result in accidents.

· 

Always use separate circuits to supply the power. Any 

   electrical work shall comply with the local laws and 

   regulations, and at the same time follow the installation 

   instruction manual to ask a qualified professional 

   electrician to carry out the work.

   Insufficient capacity or incorrect electrical work can lead 

   to electrical shock or fire.

· 

Use cables with the specified specifications, and all the 

   cables shall be reliably connected, and the wiring terminals 

   and the cables are not tensioned by any external force.

   Poor wiring and incorrect installation can lead to fire.

· 

When connecting the power cable, remote control cable or 

   transmission cable, they shall be routed orderly and placed 

   even, so that the electrical box cover can be covered tightly.

   In case that the cover cannot be covered evenly, problems 

   as electrical shock, fire or overheating of the electrical box 

   can occur.

· 

During installation, in case that any refrigerant gas leaks 

   out, please open the door and window immediately to 

   exchange the air.

   When the refrigerant gas is in contact with fire, poisonous

   gas can be generated.

· 

After complete installation, please check whether there is 

   any refrigerant gas leakage.

   In case that any refrigerant gas is leaked out in the room 

   and is in contact with any fire source, such as heater, oven 

   and furnace, poisonous gas can be generated.

· 

Before touching any electrical part, please switch off the 

   power supply.

· 

Never touch any switch with any wet hand.

   Touching any switch with any wet hand can lead to 

   electrical shock.

· 

The air conditioner must be grounded.

   Never connect the grounding cable to any gas pipe, 

   running water pipe, lighting rod and telephone line.

   Poor grounding can lead to electrical shock.

· 

In case that the connected outdoor unit is of 24 kW or 

   below, the remote control cable and the connection cable 

   shall be grounded noiselessly.

· 

An electricity leakage circuit breaker shall be installed.

   If no electricity leakage circuit breaker is not installed, 

   electrical shock or fire can occur.

· 

The indoor unit shall be installed in a place with a height 

   which cannot be reached by children – at least 1.8 m 

   above the floor.

CAUTION

· 

Please follow the installation manual to set the water 

   drainage pipe to ensure smooth water drainage, and heat 

   insulate the pipe to prevent condensate from building up.

   Poor piping can lead to water leakage and soaking articles 

   in house.

· 

The indoor unit, outdoor unit, power cable and connection 

   cable shall be separated from the TV set and radio for at 

   least 1 m, so as to prevent any electromagnetic interference 

   and noise.

   (For radios with some bands, even they are separated for 

   over 1 m, noise cannot be fully prevented.)

· 

In houses with fluorescent light (variable frequency or fast 

   start type) installed, possibly the signal transmission 

   distance of the remote control (wireless) cannot reach the 

   expected value. The farther the indoor unit is installed from 

   the fluorescent light, the better the performance is.

· 

The air conditioner is not suitable to be installed in the 

   following places:

   (a) Places in which there is mineral oil mist or spray or 

         vapor, such as in the kitchen.

         The plastic parts can be deteriorated and damaged 

         and lead to water leakage.

  1. SAFETY PRECAUTIONS……………….........…….

  2. BEFORE INSTALLATION……………….........…….

  3. SELECTING INSTALLATION SITE………….........

  4. PREPARATIONS BEFORE INSTALLATION….…. 

  5. INDOOR UNIT INSTALLATION…………………….

  6. REFRIGERANT PIPING WORK……………………

  7. DRAIN PIPING WORK…………………..................

  8. INSTALLING THE DUCT………………...……........

  9. ELECTRIC WIRING WORK……….........................

10. WIRING EXAMPLE……………………...................

11. FIELD SETTING AND TEST RUN………..........…

Содержание FXDQ-SPV1

Страница 1: ...FXDQ SPV1 EDTFVN391825 201803 Engineering Data 50 Hz...

Страница 2: ......

Страница 3: ...ams 10 6 Electric Characteristics 11 7 Safety Devices Setting 12 8 Capacity Tables 13 8 1 Cooling Capacity for Te Auto 13 8 2 Cooling Capacity for Te 6 C 13 8 3 Cooling Capacity for Te 9 C 14 8 4 Heat...

Страница 4: ...5 2 1 Lineup Capacity range 2 2 kW 2 8 kW 3 6 kW 4 5 kW 5 6 kW 7 1 kW 0 8 HP 1 HP 1 25 HP 1 6 HP 2 HP 2 5 HP Capacity index 20 25 31 25 40 50 62 5 FXDQ 20SPV1 25SPV1 32SPV1 40SPV1 50SPV1 63SPV1 V1 1 p...

Страница 5: ...tion manual Drain hose Sealing pads Clamps Washers Insulation for fitting Metal clamp Washer fixing plate Screws for duct flanges Operation manual Installation manual Drain hose Sealing pads Clamps Wa...

Страница 6: ...manual Drain hose Sealing pads Clamps Washers Insulation for fitting Metal clamp Washer fixing plate Screws for duct flanges Operation manual Installation manual Drain hose Sealing pads Clamps Washers...

Страница 7: ...on manual Drain hose Sealing pads Clamps Washers Insulation for fitting Metal clamp Washer fixing plate Screws for duct flanges Operation manual Installation manual Drain hose Sealing pads Clamps Wash...

Страница 8: ...FXDQ SPV1 EDTFVN391825 6 3 Dimensions FXDQ20SPV1 FXDQ25SPV1 FXDQ32SPV1 3D071829D Unit mm...

Страница 9: ...FXDQ SPV1 EDTFVN391825 7 FXDQ40SPV1 FXDQ50SPV1 3D071831D Unit mm...

Страница 10: ...FXDQ SPV1 EDTFVN391825 8 FXDQ63SPV1 3D071830D Unit mm...

Страница 11: ...iagrams FXDQ20SPV1 FXDQ25SPV1 FXDQ32SPV1 FXDQ40SPV1 FXDQ50SPV1 FXDQ63SPV1 Refrigerant pipe connection port diameters Unit mm Model Gas Liquid FXDQ20SPV1 FXDQ25SPV1 FXDQ32SPV1 FXDQ40SPV1 FXDQ50SPV1 12...

Страница 12: ...FXDQ SPV1 EDTFVN391825 10 5 Wiring Diagrams FXDQ20SPV1 FXDQ25SPV1 FXDQ32SPV1 FXDQ40SPV1 FXDQ50SPV1 FXDQ63SPV1 3D099151...

Страница 13: ...FXDQ SPV1 EDTFVN391825 11 6 Electric Characteristics FXDQ20SPV1 FXDQ25SPV1 FXDQ32SPV1 FXDQ40SPV1 FXDQ50SPV1 FXDQ63SPV1 4D090515...

Страница 14: ...50 V 5 A Fan motor thermal fuse C Fan motor thermal protector C OFF 130 5 ON 83 15 OFF 130 5 ON 83 15 OFF 130 5 ON 83 15 Model FXDQ40SPV1 FXDQ50SPV1 FXDQ63SPV1 Printed circuit board fuse A1P 250 V 5 A...

Страница 15: ...gth Please confirm that the corrected capacity of the VRV system satisfies the required heat load 2 shows rated condition 8 2 Cooling Capacity for Te 6 C Model Capacity indication Indoor air temp 14 C...

Страница 16: ...These capacity tables are for use when selecting a VRV indoor unit The actual capacity of the VRV system depends on factors such as the selected model of outdoor units outdoor air temperature and pip...

Страница 17: ...FXDQ SPV1 EDTFVN391825 15 9 Fan Performances FXDQ20SPV1 3D072697C...

Страница 18: ...FXDQ SPV1 EDTFVN391825 16 FXDQ25SPV1 3D072698C...

Страница 19: ...FXDQ SPV1 EDTFVN391825 17 FXDQ32SPV1 3D090527...

Страница 20: ...FXDQ SPV1 EDTFVN391825 18 FXDQ40SPV1 FXDQ50SPV1 3D072702C...

Страница 21: ...FXDQ SPV1 EDTFVN391825 19 FXDQ63SPV1 3D090542...

Страница 22: ...FXDQ SPV1 EDTFVN391825 20 10 Sound Levels FXDQ20SPV1 FXDQ25SPV1 4D090507A 4D090508A...

Страница 23: ...FXDQ SPV1 EDTFVN391825 21 FXDQ32SPV1 FXDQ40SPV1 FXDQ50SPV1 4D090509A 4D090510A...

Страница 24: ...FXDQ SPV1 EDTFVN391825 22 FXDQ63SPV1 4D090511A...

Страница 25: ...FXDQ SPV1 EDTFVN391825 23 11 Centre of Gravity FXDQ20SPV1 FXDQ25SPV1 FXDQ32SPV1 FXDQ40SPV1 FXDQ50SPV1 4D072718G Unit mm 4D072719G Unit mm...

Страница 26: ...FXDQ SPV1 EDTFVN391825 24 FXDQ63SPV1 4D072720H Unit mm...

Страница 27: ...s Item Model FXDQ20SPV1 FXDQ25SPV1 FXDQ32SPV1 FXDQ40SPV1 FXDQ50SPV1 FXDQ63SPV1 Remote controller Wireless Cooling Only BRC4C66 Heat Pump BRC4C65 Wired BRC1C62 Navigation remote controller Wired remote...

Страница 28: ...ctrical shock or fire Use cables with the specified specifications and all the cables shall be reliably connected and the wiring terminals and the cables are not tensioned by any external force Poor w...

Страница 29: ...ting methods of the various functions as well as the temperature adjustment methods of the air conditioner to the user and ask the user to read the operation manual and carry out operations at the sam...

Страница 30: ...y drained off The strength of the ceiling can withstand the weight of the indoor unit The ceiling is not obviously tilted There is no hazard of possible leakage of combustible gas There is enough spac...

Страница 31: ...an be built in the new ceiling and other items purchased in the market can be used Please refer to Fig 3 Fig 3 Top ceiling Pile anchor screw Long nut or screw thread device Hoisting bolt Note The leng...

Страница 32: ...r air exchange 1 Connect the pipe Refrigerant has been filled in the outdoor unit Align the connecting section of the refrigerant pipe to the center of the flare section and firstly turn 3 4 operation...

Страница 33: ...pipe of the air supply side The flare nut section The pipe supplied on site must be heat insulated to the connecting section of the pipe In case that the pipe is exposed condensate can occur and inju...

Страница 34: ...ng band Water drainage hose 2 Large seal 5 Accessory Metal clip 1 Accessory 4mm Precautions on installing the water drainage riser pipe Case for Model FXDQ SPV1 Please confirm that the height of the w...

Страница 35: ...e air conditioner Point 12 14 or 16 Use sealing materials such as aluminum adhesive tape to seal the connection section between the flange and the air pipe on the air inlet side so as to prevent air l...

Страница 36: ...is within a place easily in contact with people please install an electricity leakage circuit breaker to prevent electrical shock 4 When an electricity leakage circuit breaker is used please use a dev...

Страница 37: ...ng cable to the electrical box When connecting the cables the cables shall be routed orderly and placed even and the electrical box cover shall not be supported up and the electrical box cover shall b...

Страница 38: ...auses as loosened cables When connected to the terminal board please use round wiring terminal with insulated sleeve In case that round wiring terminal with insulated sleeve cannot be used connect the...

Страница 39: ...Electrical Wiring Work 3 Remove the electrical box cover 4 Connect remote control 2 Slave to the terminal board of the remote control cable in the electrical box P1 and P2 No polarity 1 P 2 P 1 F 2 F...

Страница 40: ...Setting the time to display the clean air filter element signal To change the Setting for contamination level of the air filter element tell the following contents to the user The factory setting to d...

Страница 41: ......

Страница 42: ......

Страница 43: ......

Страница 44: ...rts and accessories supplied or specified by Daikin Ask a qualified installer or contractor to install those parts and accessories Use of unauthorised parts and accessories or improper installation of...

Отзывы: