FXDQ-SPV1 EDTFVN391825

38

3P347455-11H

13

(3) Please carry out test run in accordance with the 

     installation manual for the outdoor unit.

SETTING

MODE No.

FIELD SET 

MODE

11. FIELD SETTING AND TEST RUN

(The field setting of the following items shall be 

completed with the operation of the remote control 

in accordance with the on site installation conditions. 

(In case that the remote control is Type BRC1E62, 

please refer to the installation manual for the remote 

control.))

(1) Please confirm whether the electrical box cover 

     of the indoor unit and the outdoor unit have been 

     firmly covered.

     The field setting is carried out with the remote control, 

     and whether it is required to carry out setting 

     depends on the on site installation situations.

(2) According to the installation situations, when the 

     power supply is switched on, use the remote control 

     to carry out the field setting, and please follow 

     Section “FIELD SETTING” in the operation manual 

     for the remote control to carry out setting.

· 

When setting, the “MODE No.”, “FIRST CODE No.” 

   and “SECOND CODE No.” can be changed.

· 

In Section “FIELD SETTING”, the setting sequences 

   and the operating methods which can be carried out 

   with the remote control are listed. 

· 

Finally, ask the user to keep the “FIELD SETTING” 

   operation manual and the installation manual well.

11-1 Conversion of the static pressure outside the unit

· 

The Second Code No. can be converted in accordance 

   with the resistance force of the pipe.

   (The second code number is set “01” when delivered 

   from the factory.)

· 

For details, please refer to the technical documents.

Static pressure outside the unit MODE No.

Standard

Set to high static pressure

01

02

01

02

13 (23)

5

11-2 Setting the remote operated control

· 

To carry out the input switching of forced off or on/off, 

   the settings can be the ones as shown in the following 

   table, and the settings can be carried out by changing 

   the second code number.

   (The second code number is set to “01” when delivered 

   from the factory.)

External ON/OFF input

MODE No. FIRST CODE No. SECOND CODE No.

Forced off

ON/OFF operation

12 (22)

1

· 

The functions of Forced off and ON/OFF operation input 

   signal A are shown in the following table.

Forced off

ON/OFF operation

When the input signal A is “ON”, force off 

(not controlled by the remote control)

Input signal A “OFF” 

 “ON”, 

turn on the air conditioner.

When the input signal A is “OFF”, 

the remote control can be used.

Input signal A “ON” 

 “OFF”, 

turn off the air conditioner.

11-3 Setting the time to display the clean air filter 

        element signal

· 

To change the “Setting for contamination level of the 

   air filter element”, tell the following contents to the user. 

· 

The factory setting to display the clean air filter element  

   signal is 2500 hours (about 1 year).

· 

It can be set not to display the signal.

· 

When installed in a dusty place, the setting time to 

   display the clean air filter element signal should be set 

   to the low position.

· 

Please tell the user : 

  

 To prevent the air filter element 

   meshes from being blocked, the air filter element must 

   be regularly cleaned ; 

  

 The cleaning intervals set. 

MODE

No.

FIRST

CODE No.

10(20)

0

1

3

Description on setting

SECOND CODE No.

01

02

Minor / serve 

filter element 

contamination

Ultra long

life type

Long life 

type

Minor

About 

10000 hours

About 

2500 hours

Severe

About 

5000 hours

About 

1250 hours

Time interval to display the 

clean air filter element signal Long life type

Ultra long

life type

Display the clean air filter 

element signal

Display

Do not 

display

11-4 Setting when any optional part is installed

· 

Please refer to the installation manual supplied with 

   the optional part, so as to carry out the necessary 

   setting.

(Cases in which the wireless remote control is used)

· 

When the remote control used is a wireless remote 

   control, the address shall be set for the wireless remote 

   control. For detailed steps for setting, please refer to 

   the installation instruction manual for the wireless 

   remote control.

· 

When any abnormality happens, the run indicator 

   on the remote control will flash. Confirm the error 

   code on the LCD display and locate the error. 

   In the “Key points for repair” for the indoor unit, 

   there are error code explanations and error 

   descriptions. 

   In case that the following signals are displayed on 

   the display, there may be wiring errors or discontinuity 

   of the power supply. Please check again.

Display on the 

remote control

Error content

Display  “      ”

• Forced off terminal (T

1

 and T

2

) is short circuited.

• Test run is not carried out.

• 

The power supply for the outdoor unit is disconnected.

• 

The power cable for the outdoor unit is not connected.

• The transmission cable and/or the forced off cable 

   are incorrectly connected.

• The transmission cable is broken.
• The connection cables between the air conditioner 

   are reversed.

• 

The power supply for the outdoor unit is disconnected.

• 

The power cable for the outdoor unit is not connected.

• The remote control cable, the transmission cable 

   and/or the forced off cable are incorrectly connected.

• The remote control cable is broken.

Display  “      ”

Display  “      ”
Display  “      ”

Display  “      ”

No display

SECOND 

CODE No.

FIRST

CODE No.

SECOND CODE No.

FIRST CODE No.

1

2

Содержание FXDQ-SPV1

Страница 1: ...FXDQ SPV1 EDTFVN391825 201803 Engineering Data 50 Hz...

Страница 2: ......

Страница 3: ...ams 10 6 Electric Characteristics 11 7 Safety Devices Setting 12 8 Capacity Tables 13 8 1 Cooling Capacity for Te Auto 13 8 2 Cooling Capacity for Te 6 C 13 8 3 Cooling Capacity for Te 9 C 14 8 4 Heat...

Страница 4: ...5 2 1 Lineup Capacity range 2 2 kW 2 8 kW 3 6 kW 4 5 kW 5 6 kW 7 1 kW 0 8 HP 1 HP 1 25 HP 1 6 HP 2 HP 2 5 HP Capacity index 20 25 31 25 40 50 62 5 FXDQ 20SPV1 25SPV1 32SPV1 40SPV1 50SPV1 63SPV1 V1 1 p...

Страница 5: ...tion manual Drain hose Sealing pads Clamps Washers Insulation for fitting Metal clamp Washer fixing plate Screws for duct flanges Operation manual Installation manual Drain hose Sealing pads Clamps Wa...

Страница 6: ...manual Drain hose Sealing pads Clamps Washers Insulation for fitting Metal clamp Washer fixing plate Screws for duct flanges Operation manual Installation manual Drain hose Sealing pads Clamps Washers...

Страница 7: ...on manual Drain hose Sealing pads Clamps Washers Insulation for fitting Metal clamp Washer fixing plate Screws for duct flanges Operation manual Installation manual Drain hose Sealing pads Clamps Wash...

Страница 8: ...FXDQ SPV1 EDTFVN391825 6 3 Dimensions FXDQ20SPV1 FXDQ25SPV1 FXDQ32SPV1 3D071829D Unit mm...

Страница 9: ...FXDQ SPV1 EDTFVN391825 7 FXDQ40SPV1 FXDQ50SPV1 3D071831D Unit mm...

Страница 10: ...FXDQ SPV1 EDTFVN391825 8 FXDQ63SPV1 3D071830D Unit mm...

Страница 11: ...iagrams FXDQ20SPV1 FXDQ25SPV1 FXDQ32SPV1 FXDQ40SPV1 FXDQ50SPV1 FXDQ63SPV1 Refrigerant pipe connection port diameters Unit mm Model Gas Liquid FXDQ20SPV1 FXDQ25SPV1 FXDQ32SPV1 FXDQ40SPV1 FXDQ50SPV1 12...

Страница 12: ...FXDQ SPV1 EDTFVN391825 10 5 Wiring Diagrams FXDQ20SPV1 FXDQ25SPV1 FXDQ32SPV1 FXDQ40SPV1 FXDQ50SPV1 FXDQ63SPV1 3D099151...

Страница 13: ...FXDQ SPV1 EDTFVN391825 11 6 Electric Characteristics FXDQ20SPV1 FXDQ25SPV1 FXDQ32SPV1 FXDQ40SPV1 FXDQ50SPV1 FXDQ63SPV1 4D090515...

Страница 14: ...50 V 5 A Fan motor thermal fuse C Fan motor thermal protector C OFF 130 5 ON 83 15 OFF 130 5 ON 83 15 OFF 130 5 ON 83 15 Model FXDQ40SPV1 FXDQ50SPV1 FXDQ63SPV1 Printed circuit board fuse A1P 250 V 5 A...

Страница 15: ...gth Please confirm that the corrected capacity of the VRV system satisfies the required heat load 2 shows rated condition 8 2 Cooling Capacity for Te 6 C Model Capacity indication Indoor air temp 14 C...

Страница 16: ...These capacity tables are for use when selecting a VRV indoor unit The actual capacity of the VRV system depends on factors such as the selected model of outdoor units outdoor air temperature and pip...

Страница 17: ...FXDQ SPV1 EDTFVN391825 15 9 Fan Performances FXDQ20SPV1 3D072697C...

Страница 18: ...FXDQ SPV1 EDTFVN391825 16 FXDQ25SPV1 3D072698C...

Страница 19: ...FXDQ SPV1 EDTFVN391825 17 FXDQ32SPV1 3D090527...

Страница 20: ...FXDQ SPV1 EDTFVN391825 18 FXDQ40SPV1 FXDQ50SPV1 3D072702C...

Страница 21: ...FXDQ SPV1 EDTFVN391825 19 FXDQ63SPV1 3D090542...

Страница 22: ...FXDQ SPV1 EDTFVN391825 20 10 Sound Levels FXDQ20SPV1 FXDQ25SPV1 4D090507A 4D090508A...

Страница 23: ...FXDQ SPV1 EDTFVN391825 21 FXDQ32SPV1 FXDQ40SPV1 FXDQ50SPV1 4D090509A 4D090510A...

Страница 24: ...FXDQ SPV1 EDTFVN391825 22 FXDQ63SPV1 4D090511A...

Страница 25: ...FXDQ SPV1 EDTFVN391825 23 11 Centre of Gravity FXDQ20SPV1 FXDQ25SPV1 FXDQ32SPV1 FXDQ40SPV1 FXDQ50SPV1 4D072718G Unit mm 4D072719G Unit mm...

Страница 26: ...FXDQ SPV1 EDTFVN391825 24 FXDQ63SPV1 4D072720H Unit mm...

Страница 27: ...s Item Model FXDQ20SPV1 FXDQ25SPV1 FXDQ32SPV1 FXDQ40SPV1 FXDQ50SPV1 FXDQ63SPV1 Remote controller Wireless Cooling Only BRC4C66 Heat Pump BRC4C65 Wired BRC1C62 Navigation remote controller Wired remote...

Страница 28: ...ctrical shock or fire Use cables with the specified specifications and all the cables shall be reliably connected and the wiring terminals and the cables are not tensioned by any external force Poor w...

Страница 29: ...ting methods of the various functions as well as the temperature adjustment methods of the air conditioner to the user and ask the user to read the operation manual and carry out operations at the sam...

Страница 30: ...y drained off The strength of the ceiling can withstand the weight of the indoor unit The ceiling is not obviously tilted There is no hazard of possible leakage of combustible gas There is enough spac...

Страница 31: ...an be built in the new ceiling and other items purchased in the market can be used Please refer to Fig 3 Fig 3 Top ceiling Pile anchor screw Long nut or screw thread device Hoisting bolt Note The leng...

Страница 32: ...r air exchange 1 Connect the pipe Refrigerant has been filled in the outdoor unit Align the connecting section of the refrigerant pipe to the center of the flare section and firstly turn 3 4 operation...

Страница 33: ...pipe of the air supply side The flare nut section The pipe supplied on site must be heat insulated to the connecting section of the pipe In case that the pipe is exposed condensate can occur and inju...

Страница 34: ...ng band Water drainage hose 2 Large seal 5 Accessory Metal clip 1 Accessory 4mm Precautions on installing the water drainage riser pipe Case for Model FXDQ SPV1 Please confirm that the height of the w...

Страница 35: ...e air conditioner Point 12 14 or 16 Use sealing materials such as aluminum adhesive tape to seal the connection section between the flange and the air pipe on the air inlet side so as to prevent air l...

Страница 36: ...is within a place easily in contact with people please install an electricity leakage circuit breaker to prevent electrical shock 4 When an electricity leakage circuit breaker is used please use a dev...

Страница 37: ...ng cable to the electrical box When connecting the cables the cables shall be routed orderly and placed even and the electrical box cover shall not be supported up and the electrical box cover shall b...

Страница 38: ...auses as loosened cables When connected to the terminal board please use round wiring terminal with insulated sleeve In case that round wiring terminal with insulated sleeve cannot be used connect the...

Страница 39: ...Electrical Wiring Work 3 Remove the electrical box cover 4 Connect remote control 2 Slave to the terminal board of the remote control cable in the electrical box P1 and P2 No polarity 1 P 2 P 1 F 2 F...

Страница 40: ...Setting the time to display the clean air filter element signal To change the Setting for contamination level of the air filter element tell the following contents to the user The factory setting to d...

Страница 41: ......

Страница 42: ......

Страница 43: ......

Страница 44: ...rts and accessories supplied or specified by Daikin Ask a qualified installer or contractor to install those parts and accessories Use of unauthorised parts and accessories or improper installation of...

Отзывы: