[Wiring Examples]
CAUTION
In case that the connected outdoor unit is 24 kW
or below, please comply with the following items.
·
For the remote control cable and transmission cable,
always use shielded cable, and carry out noiseless
grounding. (
✩
and
✻
section)
·
In case that wired remote control is used, always use
an embedded remote control box (made of metal) on
the remote control, and connect the noiseless
grounding cable to the embedded remote control box.
Then, ground the embedded remote control box
additionally.
·
In case that wireless remote control is used, always
use an embedded remote control box (made of metal)
on the remote control signal receiving assembly, and
connect the noiseless grounding cable to the embedded
remote control box.
Then, ground the embedded remote control box
additionally.
·
Recommended embedded remote control box to be
used : KJB111A (optional).
System 1 Use 1 remote control to control 1
indoor unit
F
T
1
L
1
1
1
P
P
2
P
N
1
2
P
T
F
2
F
P
F
1
2
2
2
P
1
N
2
P
2
F
IN/D
1
OUT/D
1
P
F
2
F
1
P
L
F
1 2
T
2
T
1
P P
2
1
F
2
N
F
L
1 2
T T
P
L N
L N
L N
Power supply
single phase
1~ 220-240 V
50 Hz
Outdoor unit
Power supply
single phase
1~ 220-240 V
50 Hz
Power supply
single phase
1~ 220-240 V
50 Hz
Indoor unit A
Indoor unit B
The last
indoor unit
Remote control
(Optional)
Remote control
(Optional)
Remote control
(Optional)
Fig. 16
System 3 Case with BS device installed
L N
F
F
1
2
F
F
1
2
F
F
1
2
F
F
1
2
IN/D
IN/D
D
/
T
U
O
D
/
T
U
O
1
P P
2
1
F
2
N
F
L
1
2
T T
1
P
2
P
Fig. 18
Power supply
single phase
1~ 220-240 V
50 Hz
Outdoor unit
BS device
Indoor unit A
Remote control
(Optional)
(Notes when connecting the power cable)
·
Never connect two cables with different cable diameters
to the same power terminal. (Overheating can occur
due to causes as loosened cables.)
·
When connected to the terminal board, please use
round wiring terminal with insulated sleeve. In case
that round wiring terminal with insulated sleeve cannot
be used, connect the cable of the same cable diameter
to both sides of the terminal, as shown in the figure.
Insulating sleeve
Round wiring terminal
Power cable
Connect cables of the
same cable diameter to
both sides respectively.
Never connect cable of the
same cable diameter to the
same side.
Never connect cable
of different cable
diameters.
Risks as overheating can happen due to causes as
loosened cables, so please always comply with the
following items.
·
Please use power cable of the specified specifications,
and firmly connect the power cable, and then confirm
whether the power cable is pulled by any external force
in the point of the terminal board.
·
When tightening the terminal screw, please use a
suitable screw driver. In case that the screw driver
head is too narrow, the screw head can be damaged,
and the screw may not be tightened.
·
In case that the terminal screw is over-tightened, it can
be damaged.
·
For the tightening torque of the terminal screw,
please refer to the following table.
Terminal
Tightening torque (N
•
m)
Terminal board for the remote control /
transmission cable (6P)
Terminal board for the power supply (3P)
Terminal for noiseless grounding (M4)
0.79 - 0.97
1.18 - 1.44
1.44 - 1.94
L N
1
P
2
P
1
P
2
P
1
P
2
P
1
P P
2
1
F
2
N
F
L
L N
1
2
F
F
1
2
F
F
1
2
T T
1
P P
2
1
F
2
F
1
2
T T
1
2
1
F
2
F
1
2
T T
IN/D OUT/D
System 2 Control by group or double control for
one unit
Fig. 17
Power supply
single phase
1~ 220-240 V
50 Hz
Outdoor
unit
Note) In case of control by group, there is no
need to enter the address of the indoor unit.
(When the power supply is switched on,
automatic setting will be carried out.)
Indoor unit A
Indoor unit B
The last
indoor unit
Case of control
by group
Remote control
(Optional)
Remote
control
Remote
control
(Optional)
Use 2 remote controls
to control 1 unit
L N
P P
Содержание FXDQ-SPV1
Страница 1: ...FXDQ SPV1 EDTFVN391825 201803 Engineering Data 50 Hz...
Страница 2: ......
Страница 8: ...FXDQ SPV1 EDTFVN391825 6 3 Dimensions FXDQ20SPV1 FXDQ25SPV1 FXDQ32SPV1 3D071829D Unit mm...
Страница 9: ...FXDQ SPV1 EDTFVN391825 7 FXDQ40SPV1 FXDQ50SPV1 3D071831D Unit mm...
Страница 10: ...FXDQ SPV1 EDTFVN391825 8 FXDQ63SPV1 3D071830D Unit mm...
Страница 17: ...FXDQ SPV1 EDTFVN391825 15 9 Fan Performances FXDQ20SPV1 3D072697C...
Страница 18: ...FXDQ SPV1 EDTFVN391825 16 FXDQ25SPV1 3D072698C...
Страница 19: ...FXDQ SPV1 EDTFVN391825 17 FXDQ32SPV1 3D090527...
Страница 20: ...FXDQ SPV1 EDTFVN391825 18 FXDQ40SPV1 FXDQ50SPV1 3D072702C...
Страница 21: ...FXDQ SPV1 EDTFVN391825 19 FXDQ63SPV1 3D090542...
Страница 22: ...FXDQ SPV1 EDTFVN391825 20 10 Sound Levels FXDQ20SPV1 FXDQ25SPV1 4D090507A 4D090508A...
Страница 23: ...FXDQ SPV1 EDTFVN391825 21 FXDQ32SPV1 FXDQ40SPV1 FXDQ50SPV1 4D090509A 4D090510A...
Страница 24: ...FXDQ SPV1 EDTFVN391825 22 FXDQ63SPV1 4D090511A...
Страница 26: ...FXDQ SPV1 EDTFVN391825 24 FXDQ63SPV1 4D072720H Unit mm...
Страница 41: ......
Страница 42: ......
Страница 43: ......